HTP EV-80 User Manual
Page 6
6
LP-04 REV. 4.15.14
Incorrect ambient conditions can lead to damage to the heating system and put safe operation at risk. Ensure that the installation
location adheres to the information included in this manual. Failure to do so could result in property damage, serious personal injury, or
death.
Failure of water heater or components due to incorrect operating conditions IS NOT covered by product warranty.
1. Installation Area (Mechanical Room) Operating Conditions
Ensure ambient temperatures are higher than 32
o
F/0
o
C and lower than 104
o
F/40
o
C.
Avoid continuously high levels of humidity
Never close existing ventilation openings
The service life of the water heater’s exposed metallic surfaces, such as the junction box, as well as internal surfaces, such as the
heating elements, are directly influenced by proximity to damp and salty marine environments. In such areas, higher concentration
levels of chlorides from sea spray coupled with relative humidity can lead to degradation of water heater components.
This water heater is certified for indoor installations only. Do not install the water heater outdoors. Outdoor installations ARE NOT
covered by warranty. Failure to install this water heater indoors could result in substantial property damage, severe personal injury, or
death.
2. Check for nearby connections to:
System water piping
Electrical power
Choose a location for the water heater as centralized to the piping system as possible.
3. Check area around water heater. Remove any combustible materials, gasoline, and other flammable liquids.
This water heater must not be located near flammable liquids such as gasoline, butane, liquefied propane, adhesives, solvents, paint
thinners, etc., as the controls of this water heater could ignite these vapors and cause an explosion, resulting in property damage,
severe personal injury, or death.
4. If the water heater is to replace an existing water heater, check for and correct any
existing system problems, such as:
System leaks
Location that could cause the system and water heater to freeze and leak.
Incorrectly-sized expansion tank
5. All piping should be insulated. Additionally, place the water heater so that the drain,
controls, and inlets/outlets are easily accessible.
If you do not provide the minimum clearances shown, it might not be possible to service
the heater without removing it from the space.
NOTE: When installing in a zero clearance location, it may not be possible to read or
view some product labeling. It is recommended to make note of the water heater model
and serial number.
6. This water heater must be installed vertical on a level surface.
Figure 2
– Recommended Clearance