Specifications

Specifications

Temperature

Operating

Storage

0° to 40° C (32° to 104° F)
-15° to 45° C (5° to 113° F) charge the battery module(s)

every six months

This unit is intended for indoor use

only. Select a location sturdy

enough to handle the weight.
Do not operate the UPS where

there is excessive dust or the

temperature or humidity are

outside the specified limits.
Be sure the air vents on the UPS

are not blocked.
Environmental factors impact

battery life. High temperatures,

poor utility power, and frequent,

short duration discharges will

shorten battery life.

Maximum

Elevation

Operating

Storage

3,000 m (10,000 ft)
15,240 m (50,000 ft)

Humidity

0 to 95% relative humidity, non-condensing

Weight

18 kg (40 lbs) without battery module
68 kg (150 lbs) with battery module
25 kg (55 lbs) each battery module

68 kg (150 lbs)

Dimensions

H x W x D

133 mm x 283 mm x 660 mm
5.24 in x 11.14 in x 26 in

Maximum Number of External Battery Packs Supported by the

Smart-UPS XL

10

Voltage

48 V