Installation options, Minimum space requirements – A.O. Smith BFM - 120 User Manual
Page 6

www.aosmithinternational.com
X
Y
V
W
W
Y
V
X
X1
Y1
V
W
X2
Y2
V
W
W
Y
V
X
BFM 30-80
BFM 100-120
Data subject to change INT/1108/BFM/02
Terms and conditions apply
, please refer to our website.
Flue systems BFM
Installation options
Concentric
x
x
x
-
-
Parallel
-
-
-
x
x
Diameter (mm)
80/125 100/150 130/200 2 x 130
2 x 130
Max. length (m)
7
7
7
7
7
Max. 45/90° bends a pipe
2
2
2
2
2
Concentric flues
It is not permitted to use more than the specified number of
bends, even when the duct is shorter than the maximum length.
A 45° bend is equivalent to a 90° bend.
Parallel flues
The parallel flue of a BFM 100 of 120 unit should always be
connected to the wall or roof penetration using the standard
transition piece (0306801). The two ducts shall not terminate
in different pressure zones.
Note: horizontal flue runs must be installed with a fall of at least
5 mm per metre.
BFM 30
BFM 50
BFM 80
BFM 100
BFM 120
A BFM water heater should be installed according category
C13 or C33.
C13
C13
C33
C33
Flue systems BFM
Minimum space requirements
Minimal space for wall duct (mm)
V
550
550
640
W
725
790
940
X
2115
2165
2190
Y
1195
1215
1310
Y *
745
765
860
V
700
700
W
1000
1000
X1
2480
2480
Y1
955
955
X2
2140
2140
Y2
1320
1320
Y2 *
870
870
Minimal space for roof duct (mm)
V
1230
1310
1610
W
605
645
1000
X
3575
3615
3580
Y
1575
1615
1560
Y **
625
665
610
V
2560
2560
W
1000
1000
X
3580
3580
X **
2630
2630
Y
1560
1560
Y **
610
610
For the parts numbers of components and flue gas ducts, etc.
please refer to the “Maintenance and accessories” chapter.
BFM 30
BFM 50
BFM 80
BFM 100
BFM 120
Ш80/125 Ш100/150 Ш130/200 2 x Ø130 2 x Ø130
* Distance without concentric pipe between bend and wall duct.
** Distance without concentric pipe between appliance and roof duct.