Ransburg, Air line heater / filter heater - safety – Ransburg Air Line and Filter Heater A13230 User Manual
Page 4

Air Line Heater / Filter Heater - Safety
Ransburg
LN-9811-14.1
2
Spray Area
AREA
Tells where hazards
may occur.
HAZARD
Tells what the hazard is.
SAFEGUARDS
Tells how to avoid the hazard.
Fire Hazard
Improper or inadequate oper-
ation and maintenance proce-
dures will cause a fire hazard.
Protection against inadvertent
arcing that is capable of causing
fire or explosion is lost if any
safety interlocks are disabled
during operation. Frequent pow-
er supply shutdown indicates a
problem in the system requiring
correction.
Fire extinguishing equipment must be present in
the spray area and tested periodically.
Spray areas must be kept clean to prevent the
accumulation of combustible residues.
Smoking must never be allowed in the spray area.
The high voltage supplied to the atomizer must
be turned off prior to cleaning, flushing or main-
tenance.
When using solvents for cleaning:
•
Those used for equipment flushing should
have flash points equal to or higher than
those of the coating material.
•
Those solvents used for cleaning must have a
flash point at minimum of 5
o
C (9
o
F) greater than
the ambient temperature. It is the end users
responsibility to insure this condition is met.).
Spray booth ventilation must be kept at the rates
required by NFPA-33, OSHA, country, and local
codes. In addition, ventilation must be main-
tained during cleaning operations using flam-
mable or combustible solvents.
Electrostatic arcing must be prevented. Safe
sparking distance must be maintained between
the parts being coated and the applicator. A dis-
tance of 1 inch for every 10KV of output voltage
is required at all times.
Test only in areas free of combustible material.
Testing may require high voltage to be on, but
only as instructed.
Non-factory replacement parts or unauthorized
equipment modifications may cause fire or injury.
If used, the key switch bypass is intended for use
only during setup operations. Production should
never be done with safety interlocks disabled.
Never use equipment intended for use in water-
borne installations to spray solvent based materials.
The paint process and equipment should be
set up and operated in accordance with NFPA-
33, NEC, OSHA, local, country, and European
Health and Safety Norms.