Fault descriptions (continued) overload fault (ol), Low current set point fault (lc), Current limit fault (cl) – Ransburg GMS Ground Monitoring System A12520-XXXX User Manual
Page 29
LN-9265-09.2
29
FAULT DESCRIPTIONS (continued)
Overload Fault (OL)
This fault will occur if the current output reaches 90uA.
Remove the condition causing excess microamps and reset the fault. Typically the target distance from the probe to the
part is too close. Back up target distance and re-calibrate.
Low Current Set point Fault (LC)
This fault will occur if the set point is set below a factory preset threshold. This is to prevent unacceptable calibration
values. If this occurs use an insulation test meter with at least 1KV output (Megger), to check that the target is properly
grounded, and verify the target distance is 4 inches, then re-calibrate the unit. To recover from a LC fault the calibration
must be set very quickly, then go back and allow the voltage to settle and reset the set point again.
Current Limit Fault (CL)
This fault will occur if the output current exceeds the maximum current by more than 20 uA for 2-3 seconds. If this oc-
curs, reset the fault from the applicator or control unit. If this fault occurs repeatedly, investigate the main PC board or
applicator barrel for the cause.