Operation

12

NetworkAIR Rack Air Removal Unit Installation

Temperature Override in each Fan Speed Mode

kW mode

Exhaust temperature
mode

Remote mode

Temp Override
Enabled

Fan speed will increase
when rack equipment
exhaust temperature
reaches 40.5° C

(

105° F)

No Effect

Depends on the fan speed
selection of the remote
device. Same as kW or
exhaust temperature mode.
In kW mode the
temperature override
setpoint can be set to
32.2–51.6° C (90–125°
F)

Temp Override
Disabled

No Effect

No Effect

No Effect

Note

If a Computer Room Air Conditioner fails, the subsequent rise in ambient temperature
can cause the temperature override to activate. Increasing the fan speed can have an
impact on the airflow in the room.