Fire Fighting Enterprises FIRERAY 5000 4-Head (Legacy) User Manual
Page 2
• All functions can be performed in ‘Lo A’
mode (default) (10, 12, 14 or 16 mA
for 1, 2 ,3 or 4 Detectors found)
• The system will default to ‘Lo A’ mode
when power is applied
• Select ‘Hi A’ (50mA) to enable faster
beam movement during Auto-Align,
Hand Align and Laser Targeting
• After installation, set the system back
to ‘Lo A’
7. Select Power Mode
1. Use
to move
between icons in the
Engineering Menu, to
highlight the icon shown
3. Use
to move to
required item
2. Press
to select
4. Use
to
change selection
5. Press
to accept
Press
to cancel
• Select 8-50m (default) or 100m
• It is possible to set the range of
each invidual Detector
9. Select Distance
between Detector
and Reflector
• Select Detector to be accessed
• All Detectors need to be aligned
separately
• Steps 9 to 12 explain how to
align individual Detectors
8. Select Detector
1
2
3
4
The system will signal Fault while in this mode
The LASER is used to align the Detector with the Reflector.
It is an approximate alignment tool only. After Auto-Align
the LASER will not necessarily be pointing on the Reflector
• Use
to move the LASER as close to the
Reflector as possible
• One press of an arrow key results in one movement of
the Detector head
• Press
or
to turn off the LASER and return to the
Settings menu
• Refer to User Guide page 20 for troubleshooting if
LASER is not visible
LASER RADIATION - AVOID
DIRECT EYE EXPOSURE
POWER OUTPUT < 5mW
CLASS IIIa LASER
Wavelength 630 - 680 nm
DANGER
10. LASER Targeting
• Select ‘Auto’ to automatically
align the infrared beam
• Signal Strength will be shown
during Alignment
• If the LASER is turned on it
will not necessarily be
pointing on the Reflector after
‘Auto’ is run - this is normal
11. ‘Auto’ Alignment
LoA: 7 minutes
HiA: 4 minutes
5. Enter Pass Code to
Access Engineering Menu
4. Apply power
• ‘E-02’ at this stage is
normal
2 seconds
15 seconds
40 seconds
• Default Pass Code: 1 2 3 4
•
Change digit
•
Move between digits
•
Accept
One System Controller can be used to
control and monitor up to four Detector
heads.The ‘#’ symbol in this guide is
used to represent the number of the
Detector currently selected (1, 2, 3 or 4).
LED indicator must face downward
3. Fitting the Product
• An incorrect Pass Code will return the
display to the Pass Code entry screen
• Three incorrect attempts will lock access
for three minutes
6. Find Detectors
60 seconds
• Press tick to enable ‘Found’
Detectors
• Any unused Detector channels
are switched off
• Press
to re-scan if number is
incorrect
This will be
the number of
Detectors
found
• ‘Find’ is automatically displayed
the first time this process is run.
‘Find’ can also be accessed in the
System Controller settings menu
Press
for Pass Code screen:
ENGLISH FINAL - A3 QSG:Layout 1 27/01/2010 09:57 Page 2