8. Servicing and Maintenance
During Operating Mode, the following states will be indicated:
Normal (no Fault or Fire) – Amber LED will flash every 10 seconds (EN approved model)
or not flash at all (UL approved model)
Fire/Alarm – Red LED will be on continuously, and Fire Relay will close
Fault – Amber LED on continuously, and Fault Relay will open
Compensation Fault – Amber LED flashes every 2 seconds
A Compensation Fault will occur when the Detector can no longer compensate for signal
loss due to dust/dirt build-up on the lenses and/or Reflector. A Compensation Fault can be
cleared by cleaning the Reflector and Detector lenses using a dry lint-free cloth, and then re-
aligning the beam. Compensation Faults can be avoided by periodic cleaning of the Reflector
and Detector before compensation limit is reached.
9. Technical Data
Operating Range (50 metre Detector)
5 to 50 metres
Operating Range (100 metre Detector)
50 to 100 metres
Supply Voltage limits
10.2Vdc to 30Vdc
Quiescent Current (no LED’s illuminated) <4mA
Alarm/Fault
Current
<15
mA
Power Down Reset Time
10 seconds
Operating Temperature (EN)
-10
C to 55C
Operating Temperature (UL)
32
F to 100F
Relative
Humidity 93%
(non-condensing)
Tolerance to Beam Misalignment at 35% Detector 1.0, Prism 5.0
Fire
Alarm
Thresholds
2.50dB
(25%), 3.74dB (35%), 6.02dB (50%)
Optical
Wavelength
880nm
Head Maximum Size
Width 130mm, Height 210mm, Depth 120mm
Weight
770
gms
IP
rating
IP50