E-Mon E-PS-S-HV-RTU User Manual
Page 38

Appendix: Technical Specifications
32
Surge – IEEE C62.41.2-2002
100kHz ring wave
1.2/50 µs – 8/20 µs
6kV / 0.5kA
6kV / 3kA
Magnetic field – ANSI C12.1
FTB – IEC 61000-4-4, level 4
4kV – measuring inputs
2kV – I/O and com.
SWC – IEEE C37.90.1
2.5kV – measuring inputs, I/O an
com.
Electromagnetic RF Fields – ANSI C12.1
20V/m @ 200kHz – 10GHz
Immunity
ESD - IEC61000-4-2
15KV – air
Emission
Radiated / Conducted - FCC/CFR 47 p.15
Class B
ANSI C12.1
Safety
Insulation, ANSI C12.1
2.5 KV r.m.s. @ 1mn
Mechanical Shock - IEC 60068-2-27 :1987 / ANSI
C12.1: 2008
15g @ 11ms
Mechanical Vibration - IEC 60068-2-6 :1987 /
ANSI C12.1: 2008
0.5g @ 30-350 Hz
Transportation drop and vibration – ISTA 1A /
ANSI C12.1
Operational temperature – ANSI C12.1
-40 ºC to 75 ºC
Storage temperature – ANSI C12.1
-40 ºC to 85 ºC
Environment
Humidity – ANSI C12.1
Measurements
and Accuracy
ANSI C12.1
Active Energy measurement - ANSI C12.20 class
10/20
Class 0.2S
PQ methods – IEC 61000-4-30
Class A
Harmonics & Interharmonics measurements – IEC
61000-4-7
Class I
Flicker measurements – IEC 61000-4-15
Class I
Power Quality
Report – EN50160