Power supply, Input/output ports – E-Mon E-PS-S-HV-RTU User Manual
Page 34

Appendix: Technical Specifications
28
Power Supply
Power supply
Supplied from Monitored Voltage inputs
Three Phase PS, Rated Inputs (L-N) 50/60 Hz
120 – 277V AC ± 20%
Operating voltage range
96 – 550V AC
Insulation Dielectric withstand
2500V AC @ 1mn
Operating Temperature range
-40ºC to + 75ºC
Output voltage
+12V DC ± 5%
480V model
standard
(direct)
Burden per phase
6VA
Three Phase PS, Rated Inputs 50/60 Hz
57.73 – 120V AC ± 20%
Operating voltage range
47 – 250V AC
Insulation Dielectric withstand
2500V AC @ 1mn
Operating Temperature range
-40ºC to + 75ºC
Output voltage
+12V DC ± 5%
120 V model optional
(via PT)
Burden per phase (w/o AUX. PS)
Burden per phase (w. AUX. PS)
6VA
<0.1VA
Auxiliary AC/DC Power supply
1
Operating Temperature range
-40ºC to + 75ºC
Rated Input, 0-400 Hz
50-288V AC, 90-290V DC
Isolation
2500V AC @ 1mn
Output voltage
+12V DC ± 5%
Burden
6VA
AC/DC
Optional module
Terminals for wires size
3 x 2.5 mm
2
pig-tail cable
Battery for RTC
and SRAM
Minimum operation reserve 48 h. – if no use of battery
(According to AS 1284.7/IEC 1038)
Total reserve capacity shall be not less than 2000h –
with use of battery. (According to AS 1284.7/IEC 1038)
Up to 3 years
More than 10 years service battery life (According to AS
1284.7/IEC 1038)
Input/Output ports
Fast Status input
Digital Input optically isolated
Dry contacts, internally wetted
24V DC
Resistance of open contact sensing
> 1Mohm
Resistance of closed contact sensing
< 100 Ohm
Sampling rate
1 ms
Insulation Dielectric withstand
2500V AC @ 1mn
2DI basic
8DI
Optional module
2
Terminals for wires size
10 x 2.5 mm
2
cable
RELAY OUTPUT
Digital output – SSR optically isolated
1
1 relay (Form C)
0.5A @ 250V AC/DC
Operation time
Release time
1 ms
1 ms
Relay Output - KYZ
basic
Insulation Dielectric withstand
2500V AC @ 1mn
1
Available in 120V model option only
2
Factory/Meter shop installable