7 rs-485 wiring (continued), Daisy-chain method – E-Mon E32-6003200REZ7KIT User Manual
Page 20

CLASS 3200 METER
62-0390-02
20
6.7 RS-485 Wiring (continued)
* An alternate version of firmware is available that replaces Modbus RTU with BACnet
MS/TP.
The meter must be ordered with this option if BACnet is desired instead of
Modbus.
There are two connection methods, daisy-chain and wire terminal, for RS-485
communications.
Daisy-Chain Method
This is the simplest method for connecting meters together.
Fig. 9. Daisy-chain Configuration.
1. Connect the +(high) terminal of PORT 1 of each meter together so that the + ter-
minals on all meters are linked, + to + to +...
2. Connect the -(low) terminal of PORT 1 of each meter together so that the - termi-
nals on all meters are linked, - to - to -...
3. Connect the GND terminals of PORT 1 to meter 1 ONLY. The GND terminals
should not be linked to each meter.
4. Torque screws to 2.2 in-lb.
Fig. 10. RS-485 Terminal.
M32776
M33195
RS-485
TERMINAL
- E32-6001600REZ7KIT E32-600800-REZ7KIT E32-600400-REZ7KIT E32-600200-REZ7KIT E32-600100-REZ7KIT E32-4803200REZ7KIT E32-4801600REZ7KIT E32-480800-REZ7KIT E32-480400-REZ7KIT E32-480200-REZ7KIT E32-480100-REZ7KIT E32-4003200REZ7KIT E32-4001600REZ7KIT E32-400800-REZ7KIT E32-400400-REZ7KIT E32-400200-REZ7KIT E32-400100-REZ7KIT E32-2083200REZ7KIT E32-2081600REZ7KIT E32-208800-REZ7KIT E32-208400-REZ7KIT E32-208200-REZ7KIT E32-208100-REZ7KIT