beautypg.com

MaxPower Corp GE LP11 UL 924 User Manual

Page 3

background image

Modifications reserved

Page 3/5

TDS_LPE_11U_6K0_10K_1UL_V010.doc

Technical Data Sheet LP 11 924 Series 6 & 10 kVA

Battery charger

Battery charging characteristic

IU (DIN 41773) constant current charging until floating voltage, then constant

voltage charging + boost charge

DC input voltage range

350 - 450 V

DC output voltage (Float/Boost)

271/295.5V

Output current limitation

A

4.2

4.2

Recharge time

80% capacity

20 hours

24 hours

Battery data

Battery type

Sealed and maintenance free (VRLA=Valve Regulated Lead Acid)

Float voltage at 25°C

271 V

Number of 12V batteries

20x78Ah

20x91Ah

Standard backup time at 100% load

PF=0.8

Minutes

150

93

Output converter (inverter)

Full load output power at PF=0.8

kVA

6

10

Full load output power with resistive load

kW

4.8

8

Full load AC output voltage

120, 208, 220, 230, 240, 277V

Output voltage waveform

Sine wave

Output voltage tolerance:

- static resistive load

+/- 1%

- dynamic mean deviation over half cycle

(load step 0-100-0%)

+/- 2%

- with measured non-linear load 2.5:1

+/- 2%

- recovery time to +/-1%

10ms

Overload capability (battery operation)

110%: 20 min., 130%: 3.5 min., 150%: 2 min.

Short circuit capability (240ms)

2.1 x full load current

Output frequency

50/60Hz (selectable)

Output frequency tolerance

+/- 0.1%, unless synchronized with the utility

Frequency tracking range

+/- 2, 4 or 6% of nominal (selectable)

Max. phase shift difference input-output

Harmonic distortion with linear load

1% max

Harmonic distortion with non-linear load
(EN 50091-3)

<10%

Power factor range

Any lagging or leading power factor is permitted within the specified

rating to PF=0.5

Crest factor handling capability of a non-linear load 5:1

Output power derating altitude

Up to 1000m/3281ft. no derating
Above 1000m/3281ft. 12.5% per 1000m/3281ft., max. 4000m/13124ft.

Protection

Automatic shut down (or transfer to bypass if available) in case of:
- low/high DC voltage
- overtemperature
- overload / short circuit
Output protected against connection to the mains

Short-circuit clearance capability

20% full load current within 10 ms with MCB class B

Inverter bridge

PWM and IGBT technology