P6 - SIGNAL INPUT DETAIL

Excitation return

1

+ Excitation

2

- Signal input

3

+ Signal input

4

2-Wire Process Transmitter

+

-

Excitation return

1

+ Excitation

2

- Signal input

3

+ Signal input

4

DC & Externally Powered Process

-DC
+DC

Excitation return

1

+ Excitation 2

+B Signal Input

3

Signal Ground 4

+A Signal Input

5

Signal Ground 6

Sensor 1

Power to sensor

+

-

DUAL CHANNEL PULSE SIGNAL INPUT

..

PROCESS / TOTALIZER SIGNAL INPUT

Excitation return

1

+ Excitation 2

+B Signal Input

3

Signal Ground 4

+A Signal Input

5

Signal Ground 6

Sensor 1

Sensor 2

Power to sensor

+

+

-

-

Single Powered Sensor Input

Two Powered Sensor Inputs

Excitation return

1

+ Excitation 2

+B Signal Input

3

Signal Ground 4

+A Signal Input

5

Signal Ground 6

Active and Passive Inputs

A Input 1
A Input 2
B Input 3

B Input 4

Z Input (+Excitation)

5

Z Input (Exc. return) 6

QUADRATURE SIGNAL INPUTS

Differential or Complementary Inputs

A Channel In

B Channel In

Zero Index In or
Excitation Output

A Input 1

+Excitation 2

B Input 3

Excitation return

4

Z Input 5

Signal Ground 6

Single Ended Inputs

A Channel In

B Channel In

Zero Index In

+ Power Output

- Power Output

Sensor common

P4 - ANALOG OUTPUT DETAIL

Driving a Load with 4-20 mA

Analog return 1

4-20 mA output

2

500 Ohms max

Driving a Load with 0-10V

Analog GND 1

0-10V output 2

5 kOhms min

MOUNTING FOR COOLING

AL 1

AL 2

RESET

POWER

AL 1

AL 2

RESET

POWER

AL 1

AL 2

RESET

POWER

AL 1

AL 2

RESET

POWER

AL 1

AL 2

RESET

POWER

Mount transmitters with ventilation holes at
top and bottom. Leave minimum of 6 mm (1/4")
between transmitters, or force air with a fan.

Inputs can be proximity switches, contact closures,
digital logic, magnetic pickups, or AC inputs to 250V .
Warning: Dual-channel signal grounds 4 & 6 are