Symptom gate will not open or close – Controlled Products Systems Group 1550ETL User Manual

Page 22

background image

22

SYMPTOM

Gate will not open or close.

Disconnect the solar panel or charger and measure the battery voltage. Battery should read 12 or more volts and
never drop below 11 volts when gate is operating.

Reset program switches to factory settings. .
Single Boards

# 1, # 2, # 3, # 5, # 10 ON, all others OFF

Dual Boards

# 1, # 2, # 5, # 10 ON, all others OFF
Turn #9 ON for dual gate sync

Disconnect all accessories from the circuit board - receivers, push buttons, keypads, loops, phones, intercoms, etc.

Activate the operator by momentarily shorting GND to INP
on one of the three pin connectors.

If the operator works, reconnect each accessory individually
starting with push button and test operation.

Disconnect actuator from circuit board and inspect pins in the connector for damage or
poor connections.

Check for proper limit switch configuration (multimeter required) on the connector from
the actuator:

GATE IN OPEN POSITION .......Orange & Green wires are shorted, White & Green wires are open.
GATE IN CLOSED POSITION .. White & Green wires are shorted, Orange & Green wires are open.
GATE IN MID TRAVEL............ White, Green, & Orange wires are open, no shorts.

Replace circuit board.

1 ON
2 ON
3 ON

4 off
5 ON
6 off
7 off
8 off

9 off

10 ON

G

N

D

I
N

P

U
T

1

2

V

Momentarily short
with a piece of wire
or needle nose.

Control board in HARD SHUT DOWN mode.

Short the GND and UL connections on the lower left set of connectors and test.