8.
Regeneration Cycle Step Programming (Display Code 1 – 6)
Use this program step to program the Regeneration Cycle step times.
— The number of Regeneration Cycle steps available is determined by the Piston / Cam type selection
entered in step #1.
— The Regeneration Cycle step being programmed is shown in the first digit of the display. Each display is
used to set the duration time in minutes of that specific step in the Regeneration Cycle.
Example: Shown for US [ u - - 1]
Default times for all of the available piston / cam types
Regeneration Cycle Step Times, in minutes, depend on the Piston / Cam selected.
NOTE: Cycle step #1 minimal setting is 1 minute.
— Use the Set Up and Set Down buttons to adjust this value.
— Press the Extra Cycle button to proceed to the next step.
Range =
0 – 199 minutes, US [ u - -1 ]
Range =
0 – 199 minutes, metric [ u - - 2 ]
Regeneration Cycle step #1 = 8 minutes
Setting: [ 1 - - 8 ]
Regeneration Cycle step #2 = 75 minutes
Setting: [ 2 - - 75 ]
Regeneration Cycle step #3 = 0 minutes
Setting: [ 3 - - 0 ]
Regeneration Cycle step #4 = 10 minutes
Setting: [ 4 - - 10 ]
Regeneration Cycle step #5 = 30 minutes
Setting: [ 5 - - 30 ]
Defaults for piston / cam type = dF
[ u - - 1 ] US
[ u - - 2 ] metric
Regeneration Cycle step #1
Default = 10
Regeneration Cycle step #2
Default = 60
Regeneration Cycle step #3
Default = 5
Regeneration Cycle step #4
Default = 10
Regeneration Cycle step #5
Default = 12
Cycle Step
dF
dFFF
FLtr
1
10 = Backwash
12 = Refill
10 = Backwash
2
60 = Brine Draw
60 = Brine Making
10 = Rapid Rinse
3
5 = 2nd Backwash
10 = Backwash
4
10 = Rapid Rinse
60 = Brine Draw
5
12 = Refill
5 = 2nd Backwash
6
10 = Rapid Rinse