Hydra-Flex Aqua-Lab + Tsunami Operating Manual User Manual
Page 10

© Hydra-Flex Inc 2011
- 10 -
PROBLEM
POTENTIAL CAUSES
SOLUTIONS
Pump not primed
Follow priming instructions
Debris in regulator
Remove regulator and clean out debris
Defective Check Valve
Replace check valve if broken
Defective Regulator
Replace Regulator
Defective Pump
Replace Pump
Incorrect Injector Flow Rate
Selection
Replace with desired injector size
System pressure too low
Ensure system pressure is set at 200 psi
Foam Generator Plugged
Ensure cleaned and clear
Downstream pluming restrictive Perform Back pressure test outlined in Section IV of this
manual, if over 66 psi, increase tube size and reduce elbows,
turns or other restrictive plumbing
Valve malfunction
Ensure valve is receiving at least 60 psi
Valve may be assembled incorrectly
Disassemble valve and clean out debris (See valve
replacement instructions)
Clogged Injector
Remove injector and blow out debris with compressed air
No water supply
Check that the system has a supply of water
Valve stuck open –
Staying open when
signal is off
Debris in valve seat
Remove and clean valve (See valve replacement instructions)
Starter Tripping
Incorrect Overload Setting
Verify overload setting versus settings found in specs page of
this document
Flow at arch is too
low
System won't
regulate up to 200
psi
No flow from injector