AMX Dual Choke Module RDA-CKM User Manual
Installation sheet, Rda-ckm dual choke module
Installation Sheet
RDA-CKM Dual Choke Module
The RDA-CKM Dual Choke Module is used for debuzzing, lamp noise
reduction, and to correct minor common neutral interactions. This unit con-
sists of dual 350 µS rise time chokes. It occupies only one enclosure space
and is useful with the RDD-DM series of integrated dimmer modules. The
module's 120 and 240-277 VAC ratings are UL and C-UL approved.
RDA-CKM UL and C-UL Ratings:
Input:
•
120 VAC, 50/60 Hz, 2400 W
•
240-277 VAC, 50/60 Hz, 2400 W
Specifications:
•
Dimensions (HW): 10.0" x 2.75" (254.00 mm x 69.85 mm)
•
Use wires rated at 75°C (167°F)
•
Torque terminals to 7 in-lbs (0.8 N/M)
•
Max. wire size: 10 AWG (4 mm²)
•
Wire stripping length: 0.28" (7 mm)
•
Weight: 6.5 lbs (2.95 kg)
•
BTU/hr: 300
Suggested Loads:
•
Incandescent
•
Low-voltage
•
Neon, cold-cathode
Caution Pre-Installation Notes:
•
All Class 1 wiring must be connected to proper terminals.
•
All control wiring must be connected to proper terminals.
•
Disconnect power while installing or connecting the unit.
•
Keep top and bottom air vents clear at all times.
•
Test loads for shorts before connecting.
•
Use low-voltage wires with a 300 volt rating or greater.
•
Use field-installed copper conductors.
•
Run all low-voltage and control wires away from heat producing parts
of the dimmer.
•
Each dimming circuit must have a separate neutral connection.
•
All electrical ratings are for continuous duty.
•
For indoor use only.
•
AC lighting loads only.