Flowline LD32‐S4_1 DeltaSpan User Manual
Page 14
![background image](/manuals/329565/14/background.png)
14 of 16
MN301040
Rev B
INSTALLATION
Step Ten
The LD31 / LD32 series is designed to operate while submerged in the actual application
liquid. Avoid installing the level transmitter along the bottom of the tank is materials
such as sludge will build up and coat/cover the transmitter. This also includes any
debris that will settle along the bottom of the tank. In these applications, it is best to
suspend the transmitter above the highest level of sludge/debris that will occur.
1. Location: Select a location where the temperature of the transmitter will be
between 0 and 176°F (‐18 to 80°C). Distance from the receiver is limited only by
total loop resistance.
2. Position: The transmitter is not position sensitive. However all standard models are originally
calibrated with the unit in a position with the pressure connection downward. Although they can be
used at other angles, for best accuracy it is recommended that units be installed in the position
calibrated at the factory.
3. Mounting: The transmitter can be mounted via several methods. It can be suspended from the
electrical cable, it can be placed resting on the bottom of the tank in either horizontal or vertical
orientation, or it can be attached to a pipe or hang wire by the 1/2˝ NPT male connection on the top of
the housing.
Interference: The DeltaSpan™ is designed to operate under the surface of the liquid in
the tank. Avoid installations where other tank requirements will cause the transmitter
to move or swing. For example: a mixer blade could cause the level transmitter to whip
around within the tank. An alternative would be to move the transmitter to a more
stable section of the tank or to install the LD31 series inside a still well/drop tube. The
still well/drop pipe will minimize the effects created by the mixer.
Termination: The cable for the DeltaSpan™ is typically terminated at a junction box
located on top of the tank. Since the vent tube is contained within the cable, the pressure
within the junction box must always be the same as the reference (typically atmospheric)
pressure for the liquid. The inside of the junction box must be clean, dry and free of
moisture. Add the optional pressure fitting (LD90‐_001) to complete the package. The
LD90‐_001 features a 2” NPT thread for mounting and a liquid tight connector to seal the
cable interface.
Note: Use caution when sealing the cable at the top of the tank. The ventilation tube
must be open and free to allow air to flow back to the pressure diaphragm. Avoid blocking
the ventilation tube by compressing the cable. Always keep the cable termination clean,
dry and free of moisture and prevent liquid from entering the vent tube.
Note: A vent Filter is provided on the end of the vent tube. If the application requires
the vent tube to be cut to length, then remove the vent filter and place on the end of the new end of the vent
tube.
Note: For extra protection against high humidity environments, Flowline offers the LD90‐3000 desiccant filter
that can be attached to the vent tube.