INSTALLATION 

Step Ten 

The LD31 / LD32 series is designed to operate while submerged in the actual application 
liquid.    Avoid  installing the  level  transmitter  along  the  bottom  of  the  tank  is  materials 
such  as  sludge  will  build  up  and  coat/cover  the  transmitter.    This  also  includes  any 
debris that will settle along the bottom of the tank.  In these applications, it is best to 
suspend the transmitter above the highest level of sludge/debris that will occur. 

1. Location:  Select  a  location  where  the  temperature  of  the  transmitter  will  be 

between 0 and 176°F (‐18 to 80°C). Distance from the receiver is limited only by 
total loop resistance. 

2. Position:  The  transmitter  is  not  position  sensitive.  However  all  standard  models  are  originally 

calibrated with the unit in a position with the pressure connection downward. Although they can be 
used  at  other  angles,  for  best  accuracy  it  is  recommended  that  units  be  installed  in  the  position 
calibrated at the factory. 

3. Mounting:  The  transmitter  can  be  mounted  via  several  methods.    It  can  be  suspended  from  the 

electrical  cable,  it  can  be  placed  resting  on  the  bottom  of  the  tank  in  either  horizontal  or  vertical 
orientation, or it can be attached to a pipe or hang wire by the 1/2˝ NPT male connection on the top of 
the housing. 

Interference:  The DeltaSpan™ is designed to operate under the surface of the liquid in 
the tank.  Avoid installations where other tank requirements will cause the transmitter 
to move or swing.  For example: a mixer blade could cause the level transmitter to whip 
around  within  the  tank.    An  alternative  would  be  to  move  the  transmitter  to  a  more 
stable section of the tank or to install the LD31 series inside a still well/drop tube.  The 
still well/drop pipe will minimize the effects created by the mixer.  

Termination:    The  cable  for  the  DeltaSpan™  is  typically  terminated  at  a  junction  box 
located on top of the tank.  Since the vent tube is contained within the cable, the pressure 
within the junction box must always be the same as the reference (typically atmospheric) 
pressure  for  the  liquid.    The  inside  of  the  junction  box  must  be  clean,  dry  and  free  of 
moisture.   Add the  optional pressure fitting (LD90‐_001)  to  complete the package.    The 
LD90‐_001 features a 2” NPT thread for mounting and a liquid tight connector to seal the 
cable interface. 

Note:    Use  caution  when  sealing  the  cable  at  the  top  of  the  tank.    The  ventilation  tube 
must be open and free to allow air to flow back to the pressure diaphragm.  Avoid blocking 
the ventilation tube by compressing the cable.  Always keep the cable termination clean, 
dry and free of moisture and prevent liquid from entering the vent tube. 

Note:  A vent Filter is provided on the end of the vent tube.  If the application requires 
the vent tube to be cut to length, then remove the vent filter and place on the end of the new end of the vent 
tube. 

Note: For extra protection against high humidity environments, Flowline offers the LD90‐3000 desiccant filter 
that can be attached to the vent tube. 

 

 

 