beautypg.com

3 technical characteristics – DE DIETRICH C 230 Eco User Manual

Page 20

background image

20

C 230 ECO

20/02/09 - 300015144-001-C

6.3 Technical characteristics

C 230-...

Unit

85

130

170

210

General
Number of sections

3

4

5

6

Burner operation

Modulating

Useful output (80/60°C) PN (G20)

minimum

kW

16

22

29

39

maximum

kW

87

113

(1)

/120

166

200

Useful output (50/30°C) PN (G20)

minimum

kW

18

24

33

44

maximum

kW

93

121

(1)

/129

179

217

Burner output (PCI) (G20)

minimum

kW

17

23

31

41

maximum

kW

89

115

(1)

/123

170

205

Combustion gas and by-products
Gas supply pressure G20

mbar

17 - 30

Gas flow rate G20 (15 °C - 1013 mbar)

minimum

m

3

/h

1.8

2.4

3.3

4.3

maximum

m

3

/h

9.4

12.2

(1)

/13

18

21.7

Gas flow rate G25 (15 °C - 1013 mbar)

minimum

m

3

/h

2.1

2.8

3.8

5.0

maximum

m

3

/h

11

14.4

20.9

25.2

Gas flow rate G27 (15 °C - 1013 mbar)

minimum

m

3

/h

2.2

3.0

4.0

-

maximum

m

3

/h

11.5

15.9

22.0

-

Gas flow rate G31

minimum

Kg/h

1.94

1.94

3.42

3.19

maximum

Kg/h

6.91

9.56

13.21

15.93

CO

2

(G20-G25) Qmin.-Qmax (Open air box)

%

9.3-8.8

9.3-8.8

9.3-8.8

9.3-8.8

CO

2

(G20-G25) Qmin.-Qmax (Closed air box)

%

9.5-9.0

9.5-9.0

9.5-9.0

9.5-9.0

CO

2

(G27) Qmin.-Qmax (Open air box)

%

9.3-8.8

9.3-8.8

9.3-8.8

-

CO

2

(G27) Qmin.-Qmax (Closed air box)

%

9.5-9.0

9.5-9.0

9.5-9.0

-

CO

2

(G31) Qmin.-Qmax (Open air box)

%

10.5-9.8

10.5-9.8

10.5-9.8

10.5-9.8

CO

2

(G31) Qmin.-Qmax (Closed air box)

%

10.7-10.0

10.7-10.0

10.7-10.0

10.7-10.0

Average nitrogen oxide emission (NOx)

mg/kWh

62

54

49

58

Average CO emission

mg/kWh

19

15

16

19

Maximum pressure at the flue gas nozzle

Pa

130

130

130

130

Combusted gas flow

(2)

minimum

Kg/h

27.2

36.7

49.5

65.5

maximum

Kg/h

149.7

193.5

(1)

/

206.9

286.0

344.9

Classification of type according to the discharge of
combusted gases and air supply

B23, B23P, C13, C33, C43, C53, C63, C83

Heating
Safety temperature

°C

110

Water setting range

°C

20 - 90

Water pressure

minimum

bar

0,8

maximum

bar

6

Water content

l

12

16

20

24

Water resistance at

T = 10K

mbar

660

540

680

720

Water resistance at

T = 20K

mbar

165

135

170

180

Electricity characteristics
Power supply voltage

V/Hz

230 / 50