beautypg.com

DE DIETRICH C 230 Eco User Manual

Page 14

background image

14

C 230 ECO

20/02/09 - 300015144-001-C

Messages are not memorised.

BL.BAD PSU

18

The PSU is not compatible with the PCU

- Switch the boiler off and switch back on
- PSU: Change them
- Set the boiler type parameter

BL. COM SU

21

Communication breakdown between PCU
and SU

Check the installation of the SU on the PCU

BL.FLAME LOS

22

Flame lost

- Wait 10 seconds
- If, after 5 attempts, the error persists, BL.FLAME LOS

changes to I-CURRENT FAIL

Check:

- Opening the gas valve on the boiler
- Gas pressure
- Setting the gas valve unit
- Check the connection of the combusted gas evacuation

and the air inlet

- Checking the heat exchanger

BL.CCE TEST

24

The cyclical leak proofing kit (CCE) has
detected a problem

- Wait 10 seconds
- If, after 5 attempts, the error persists, BL.CCE TEST

changes to CCE TEST FAIL

Check:

- Opening the gas valve on the boiler
- Gas pressure
- Correct installation of the pressure switch handling the

CCE function (Replace if necessary)

- Gas valve (Replace if necessary)
- Wiring

BL.SU ERROR

25

SU: Internal error

- Wait 10 seconds
- SU: Change them

BL.UNKNOWN

254

Blockage unknown

- Switch the boiler off and switch back on
- SU: Change them

Message

Code

no.

Probable causes

Action