DE DIETRICH MODULENS AGC 15, AGC 25, AGC 35 User Manual
Page 35

Code Faults
Cause
of the
fault
Description
Checking / solution
L40
TEST.HRU.FAIL
PCU
HRU/URC unit test error
Bad connection
External cause
Parameter incorrectly set
4
Contact the professional who takes care of
maintenance of the appliance
L250 DEF.WATER MIS.
PCU
The water pressure is too low
Hydraulic circuit incorrectly vented
Water leak
Measurement error
4
Top up with more water if necessary
4
Reset the boiler
L251 MANOMETRE FAIL
PCU
Fault on the water pressure sensor Wiring problem
The manometer is defect
Sensor pcb defect
4
Contact the professional who takes care of
maintenance of the appliance
D03
D04
OUTL S.B FAIL.
OUTL S.C FAIL.
SCU
Circuit B flow sensor fault
Circuit C flow sensor fault
Remarks:
The circuit pump is running.
The 3-way valve motor on the circuit
is no longer powered and can be
adjusted manually.
Bad connection
Sensor fault
4
Contact the professional who takes care of
maintenance of the appliance
D05
OUTSI.S.FAIL.
SCU
Outside temperature sensor fault
Remarks:
The boiler operates on BOILER
MAX
temperature.
The valve setting is no longer
ensured but monitoring the
maximum temperature of the circuit
after the valve is ensured.
Valves may be manually operated.
Reheating the domestic hot water
remains ensured.
Bad connection
Sensor fault
4
Contact the professional who takes care of
maintenance of the appliance
D07
AUX.SENS.FAIL
SCU
Auxiliary sensor fault
Bad connection
Sensor fault
4
Contact the professional who takes care of
maintenance of the appliance
D09
DHW S.FAILURE
SCU
Domestic hot water sensor fault
Remarks:
Heating of domestic hot water is no
longer ensured.
The load pump operates.
The load temperature of the dhw
tank is the same as the boiler.
Bad connection
Sensor fault
4
Contact the professional who takes care of
maintenance of the appliance
D11
D12
D13
ROOM S.A FAIL.
ROOM S.B FAIL.
ROOM S.C FAIL.
SCU
A room temperature sensor fault
B room temperature sensor fault
C room temperature sensor fault
Note:
The circuit concerned operates
without any influence from the room
sensor.
Bad connection
Sensor fault
4
Contact the professional who takes care of
maintenance of the appliance
D14
MC COM.FAIL
SCU
Communication failure between the
SCU PCB and the boiler radio
module
Bad connection
4
Contact the professional who takes care of
maintenance of the appliance
Boiler module failure
4
Contact the professional who takes care of
maintenance of the appliance
AGC 10/15 AGC 15 AGC 25 AGC 35
6. Troubleshooting
03/12/2013 - 300026080-001-03
34