Adjustment parameter FT - Tubular solar collector
function
Adjustment range: 0/1
Factory setting: 0
0: no
1: yes
If the regulator detects a temperature rise in the collector of 2 K
compared to the last measurement, the solar pump runs at full speed
for 30 seconds to measure the current average temperature.
The measured temperature thus becomes the new reference
temperature.
If the measured temperature (new reference) then increases again
by 2 K, the solar pump starts again for 30 seconds.
The regulator switches automatically to solar heating mode if the
temperature difference between the collector and the tank exceeds
the switching-on temperature difference when the solar pump is
operating or the system is stopped.
If the collector temperature falls by 2 K while the system is stopped,
the tubular solar collector activation temperature is rechecked.
Adjustment parameter Fx - Maximum flow rate
Adjustment range: 0 ... 20 l/min
Factory setting: 6.7
In order for the regulator to calculate the quantity of heat produced by
the installation (parameter kWh), input parameter Fx. The parameter
Fx is equal to the flow in litres per minute in the solar circuit.
Determine the value Fx using the following tables, according to the
configuration of the installation and the number or surface area of the
collectors. When the flow is input incorrectly, the display kWh will also
be incorrect.
The quantity of heat (kWh value) can only be used for checks
carried out for personal reasons.
Adjustment parameter MM - Operating mode
Adjustment range: 0 ... 2
Factory setting: 2
For inspection and maintenance work, it is possible to operate the
regulator in manual mode. To operate the regulator in manual mode,
it is necessary to input parameter MM from the following table.
Flat solar panels
Solar panel
installation
Area
m
2
Number of
panels
Flow rate
l/h
Flow rate
l/min
3 ... 5
1 or 2
400
6.7
6 ... 8
3 or 4
300
5
M000399
M000400
Tubular solar panels
Number of panels
Flow rate
l/h
Flow rate
l/min
minimum: 1x4
820
13.7
1x5
750
12.5
1x6
680
11.4
MM
R1
LED
0
Open
Flashing green/red
1
Closed
Flashing green/red
2
automatic
automatic
M000401