Quick-start instructions, Step a step b, Step d – Dynasonics UFX ULTRASONIC FLOW METER User Manual
Page 4
![background image](/manuals/328744/4/background.png)
4
QUICK-START INSTRUCTIONS
This manual contains detailed operating instructions for the UFX instrument.
The following condensed instructions are provided to assist an experienced
operator in basic operation of the instrument. If the operator is unfamiliar with
this type of instrument, refer to the detailed explanations located at the
corresponding letter on pages 8-11.
A. Select a transducer mounting location at least 10 pipe
diameters downstream and 5 diameters upstream of
flow disturbances (i.e. elbows, tees, valves, etc.)
B. On horizontal pipe, choose a
transducer mounting location
approximately 90 degrees from
the top of the pipe.
C. Remove rust, scale and paint
from the transducer mounting
location. Clean to bare metal.
Plastic pipes do not require
preparation.
D. Plug the transducer plug into
the transducer jack.
STEP A
STEP B
STEP D
YES
YES
NO
NO