Use an approved gas

pipe sealant at all

external threaded

connections, gas

piping used on gas

connections must

avoid sharp bends

that may restrict the

flow of gas to the

appliance. If the

connected pressure exceeds 14.0" W.C. (3.5 kPa), a

step-down regulator is required to be supplied by the

owner/operator.

Close the individual manual shut-off valve to

isolate the fryer from the gas supply piping system

during any pressure testing at test pressures equal to

or less than

1/2

psig. (3.4 kPa). The fryer and

individual shut-off valve must be disconnected

from the gas supply piping system during

any pressure testing at pressures in

excess of 1/2 psig. (3,4 kPa).

In the U.S.A., installation must conform to local
codes or, in the absence of local codes, with the
current edition of the National Fuel Gas Code,
NFPA-54 and ANSI Z83.11a CSA 1.8a 2004 (or
latest edition). In Canada, installation must be in
accordance with local codes, CAN/CGA-B149.1,
Installation for Natural Gas Burning Appliances
and Equipment
(latest edition) or CAN/CGA-
B149.2 Installation for Propane Burning
Appliances and Equipment
(latest edition).

The inlet supply line must be properly sized to

accommodate all individual appliances

simultaneously used on the same line but must

never be smaller than 3/4

"

I.D.

LEAK TESTING

Installation requires gas leak testing on all gas

piping and fittings. Use an approved electronic leak

device or a soap and water solution at all gas

connections. If bubbling appears when using a soap

and water solution, the connection must be refitted.

Never use an open flame to leak test.

INCORRECT

CORRECT

A
B

C

D

E

F

G

H

GAS INTAKE

A-G Installation elbow

B Wall Valve

C-D Three-piece union fitting

(minimum 1 per installation)

E-F End connector for the flexible tube

H Marking line

G A S C O N N E C T I O N

D A N G E R

Installation, air adjustment and/or
service work must be in accordance
with all local codes and must be
performed by a certified service
technician qualified to work on
gas appliances.

D A N G E R

NEVER USE AN OPEN

FLAME TO LEAK TEST.

I N S T A L L A T I O N

Gas Fryer Operation & Care Manual • 9