A. hemmed duct installation – Anemostat Pro Jet User Manual
Page 3
1220 Watson Center Road • Carson, CA 90745
Tel: (310) 835-7500 • Fax: (310) 835-0448
3
SLAD / Free Flo / Pro Jet Installation Instructions
A. HEMMED DUCT INSTALLATION
• Duct supports linear diffuser
• Drywall pre-installed
1. After plenum is securely fixed above the ceiling, position mounting brackets in the hem edge of the plenum so that they will line
up with the linear diffuser’s cross members (stays). The hem edge may be crimped into the hole of the mounting bracket with
pliers. This will retain the mounting bracket in position as the mounting screws are attached.
2. Before positioning the diffuser in the ceiling, remove the pattern control element/adjustment vane assembly from a
1-slot diffuser, or remove the inner vane(s) from a 2- or more-slot diffuser to expose the mounting holes in the diffuser cross
member (stay). Both the pattern control element/adjustment vane assembly and the inner vane(s) can be removed by pulling
them out of the friction clip from the face side of the diffuser. This is more easily done at the floor level.
3. Position the diffuser in the ceiling and push the No.8 x 1-3/4” screw through the diffuser cross member and screw into the
mounting bracket until the diffuser is pulled snug to the ceiling.
4. Re-attach the pattern control element/adjustment vanes assembly or vanes that were previously removed.
OUTER FRAME
ALIGNMENT STRIPS
No. 8 x 1-3/4" LONG
SHEET METAL SCREW
MOUNTING BRACKET
(FIELD INSTALLATION)
DUCT (BY OTHERS)
SEE HEM DETAIL
INNER VANE
(SNAP-IN)
CEILING
STAY
HEM DETAIL
Duct must be hemmed
as shown (On sides only)
3/8 TO 3/4
3/32
REF. DUCT
OPENING