5.0 Storage

A charged battery can be stored for up to six months but will suffer a gradual loss in capacity. If a
battery is to be put back into service in less than six months, fully recharge it every three months with
the 10 hour rate current for 14 hours.

If a battery will be stored for a period longer than six months, completely discharge it, completely
remove the electrolyte, thouroughly dry the inside, and close the vent plug of each cell.

Store the battery in a room which is clean, cool, dark and dry. When putting the battery back into
service, fi ll every cell with electrolyte as instructed in section 2.2 and then charge it fully by following
the charging procedure explained in section 3.3.

6.0 Replacement Parts

If any accessory items or component parts are missing or damaged at the time of delivery or are
found to be defective at the time of maintenance, replacements can be ordered by contacting
customer service with the following information. Part numbers and nomenclatures can be found in the
specifi cations.

Type of the battery and number of the cells

Part Number and Nomenclature

Quantity

Reasons replacements ordered (e.g., lost or damaged during the transit or deteriorated while in
use)

Destination of the shipment, which should include the name and full address of the company and,
if applicable, the name of the person responsible for receiving the shipment