0 starting the engine, continued – Alpha Technologies AlphaGen DCX3000 - Operator's Manual User Manual
Page 19

041-028-B0-003, Rev. C
19
4.0
Starting the Engine, continued
1
All battery voltage measurements are ± 1V
2
To enable forced output when the Overload Alarm LED is fl ashing, press the output button for at least 5
seconds. The Overload Alarm LED stops fl ashing. Release the output button, and then press it again for
at least fi ve seconds. The Output Indicator LED turns on steady, and power output begins. The operator
may then release the output button.
3
Engine shuts down after 1 second.
Table 4-1, Battery Voltage and Output Indications
NOTE:
To manually disconnect the Output Voltage, press the OUTPUT SW momentarily to remove voltage from the
battery pack. See Step 1 of Section 5.0, Engine Shutdown and Cable Removal.
To re-establish output voltage after manual or automatic disconnection, turn the ENGINE SW counter-
clockwise to OFF. After the engine stops, turn the ENGINE SW to ON and follow the procedures in Section
4.0, Starting the Engine.
Not Available
Not Available
Battery Voltage
0V to 2V
2V to 27V
27V to 42V
42V to 55V
>56V
Voltage Select
Switch Position
Output Indicator
(Green LED)
Overload Alarm
(Red LED)
Forced Output
36V
48V
36V
48V
36V
48V
36V
48V
36V
48V
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
FLASHING
FLASHING
OFF
FLASHING
FLASHING
OFF
FLASHING
FLASHING
ENABLED
ENABLED
ENABLED
2
1
3
3
Not Available
Not Available
Not Available
Not Available
Not Available