beautypg.com

Alpha technologies, Patented, Caution – Alpha Technologies AlphaGuard AG-CMT Installation User Manual

Page 2

background image

012-306-C0-004, Rev. D 01/2006

2 of 2

Battery Cable

Connection

Status Indicator LED

Voltage Sense

Connection

Alpha Technologies

AlphaGuard Wire Harness Installation
1. Set the BATTERY BREAKER to the OFF position.
2. Unplug the battery pack from the power supply.
3. From the diagram below, select the battery pack voltage that matches your

installation.

4. Connect the AlphaGuard wire harness to the battery pack (see chart below).

Torque to battery manufacturer’s recommendations.

5. Reconnect battery pack to the power supply, and set the BATTERY

BREAKER to the ON position.

6. Connect the wire harness to the front of the AlphaGuard box. Verify Status

Indicator LED is lit.

Battery Monitoring Cable Installation
1. Insert one end of the battery monitoring cable into the Voltage Sense

connector on the front of the AlphaGuard.

2. Connect the other end of the monitoring cable into the AUX connector

on the front of the EDSM, or to the BATT connector on a external
DOCSIS transponder.

3. Verify battery wire kit is properly connected.
4. Press and hold the STAT button on the EDSM until the RDY LED lights;

when you release, all LEDs will blink.

5. Verify Status Indicator LED on the AlphaGuard is on steady.

Alpha Technologies
3767 Alpha Way
Bellingham, WA 98226
USA
Tel: +1(360) 647 2360
Fax: +1(360) 671 4936
www.alpha.com

Alpha Technologies Ltd.
4084 McConnell Court
Burnaby, BC, V5A 3N7
CANADA
Tel: +1(604) 430 1476
Fax: +(604) 430 8908

Alpha Technologies
Europe Ltd.
Twyford House
Thorley
Bishop's Stortford
Hertfordshire
CM22 7PA
UNITED KINGDOM
Tel: +44 (0)1279 501110
Fax: +44 (0)1279 659870

Alpha Technologies GmbH
Hansastrasse 8
D-91126 Schwabach
GERMANY
Tel: +49 9122 79889 0
Fax: +49 9122 79889 21

Alphatec
339 St. Andrews Street
Suite 101
Andrea Chambers
Limassol, Cyprus
CYPRUS
Tel: +357 25 375675
Fax: +357 25 359595

Battery Monitoring Cables

Single String, 9', 36/48V:

Alpha P/N 875-510-20

Dual String, 9', 36/48V:

Alpha P/N 875-510-21

Single String, 35', 36/48V: Alpha P/N 875-510-23
Dual String, 35', 36/48V:

Alpha P/N 875-510-22

CMT
Connector

Battery
Cable(s)

For general product information and customer service (7 AM to 5 PM, Pacifi c Time), call

1-800-863-3930,

For complete technical support, call

1-800-863-3364

7 AM to 5 PM, Pacifi c Time or 24/7 emergency support

Patented

Standby power is not available while the batteries are disconnected.

CAUTION!

LED illuminates at 38.6V for 36V strings and 51.4V for 48V strings.

NOTE:

When using the Battery Monitoring Cable with XM Power Supply
and external Alpha DOCSIS Transponder, clip the black wire from
the cable kit at both ends.

+

+

+

+

12V

24V

36V

48V

Brown

Red

Yellow

Orange

+

To Battery Cable Connection

Black

48VDC

+

+

+

12V

24V

36V

36VDC

Brown

Yellow

Orange

To Battery Cable Connection

Black

+

Power Supply

Connection

Power Supply

Connection

Red

Black

Red

Black

CAUTION!