Local alarms, Remote alarms, Connections – Alpha Technologies FlexNet FMPS User Manual
Page 3: Mechanical, Battery
Specifications for Argus Technologies’ FMPS Continued
Argus Technologies Ltd.
010-592-B1 Rev A WC
Printed in Canada. © 2008 Argus Technologies Ltd. ARGUS is a registered trademark of Argus Technologies Ltd. All Rights Reserved.
Page 2 of 5
Local Alarms
System LED:
Green steady = system output normal, DC output/off = no AC or battery power
Battery LED:
Yellow steady = system on battery/off = normal mode
Replace Battery:
Red steady = replace one or two battery strings/off = batteries within parameters
Replace Battery A&B (internal): Red steady = replace one or both battery strings/off = batteries within parameters
Audible Indicator (Alarm On):
Alarm enable/disable toggle switch located on FMPS, batteries below voltage
parameters
Remote Alarms
SEE ALSO CONNECTIONS
Pin 1 Alarm Return:
Open collector return reference
Pin 2 AC Fail:
On battery
Pin 3 Replace Battery:
One or both battery strings failed periodic self-test
Pin 4 Missing Battery:
< 8 batteries
Pin 5 Battery Low:
Battery string voltage < 46.8Vdc
Connections
Output:
2x terminal blocks accepting #16 AWG (1.5mm²), parallel connections
Remote Alarms:
2x 5-position IDC #24 AWG (0.25mm²), parallel connections
Mechanical
Dimensions
FMPS:
603mm H x 356mm W x 140mm D
(23.75” H x 14” W x 5.5” D)
FMPS + Shipping Carton:
724mm H x 432mm W x 298mm D
(28.5” H x 17” W x 11.75” D)
Weight
FMPS: 11.3
kg
(25 lb.)
FMPS + Shipping Carton:
13.6 kg
(30 lb.)
Battery
Type:
4 or 8 7.2AH valve regulated lead acid (VRLA)
Model:
GS Battery Inc., OEM P/N: PX12072F2-HG
CSB, OEM P/N: GP1272F2
For compatibility with other battery models, please consult Argus factory.