6 status leds, 7 ac input power connection, 8 battery connection – Alpha Technologies FlexNet ELPM 300-48D User Manual
Page 15
15
010-322-C0-003, Rev C
1.0
Installation, continued
1.6 Status LEDs
The status LEDs are located on the front panel
of the unit. Normal operation is indicated by
the green LED ON, and the red LED OFF. LED
status indication also has a time delay when
reporting failures. The time delay is similar to
that illustrated in Section 1.5.
1.7 AC Input Power Connection
The Flexnet 300 offers switchable
AC input power capability. Slide
the input power switch (located
on the side of the housing) to the
correct voltage and plug the AC
power cord into the receptacle.
Verify that the green LED is
continuously illuminated and the
red LED begins to blink within
20 seconds, indicating that the
battery pack is not yet installed.
_
+
1.8 Battery Connection
Using a multimeter, verify that 48Vdc is present at the connection
leading from the battery pack, and the polarity is correct. Connect the
battery pack to the Battery connection on the front of the unit. Note the
shape of the Battery connectors which prevent incorrect hookup. Verify
that the red alarm LED goes out within 10 seconds.