Liberty Pumps ELV-Series OilTector User Manual
Page 6

7000 Apple Tree Avenue Bergen, NY 14416 Phone: (800) 543-2550-Fax: (585) 494-1839-www.libertypumps.com
Operation and Maintenance Manual
Page 6 of 6
DWG#7235000H
Manual 7235000H
:
Operation and Maintenance Manual
Operation and Maintenance Manual
Operation and Maintenance Manual
Maintenance
1. The preset level control must be kept clean and free of rust, mud, soap or any conductive material.
2. Every year clean probes keeping them free of debris, calcium or iron deposits.
3. Fuses in control panel are 5mm X 20mm 1/2amp for F1 and 5mm X 20mm 1amp for F2.
(Spare fuses are included for your convenience)
4. Every year replace 9 Volt Battery in Remote Alarm.
Trouble Shooting
Symptom
Possible
Cause Action
Pump does not run
Panel Power Cord Unplugged
Plug in Outlet, Check Power
Pump not plugged into panel
Plug pump to panel plug
Defective
Contactor
Replace
Contactor
Loose
level
sensor
wires Tighten
connections
Pump
failure
Replace
pump
Pump turns off before
Poor pump ground or system ground Check grounding system
bottom probe