Operation and maintenance manual page 4 of 6, Operation and maintenance manual – Liberty Pumps ELV-Series OilTector User Manual

Page 4

background image

Mounting Hole (2)

Figure 8 - Mounting

Side Screw

120VAC Wallmount

Receptacle

Figure 7 - Installing/Replacing Battery

Battery Strap

Connector

Duracell Model

MX1604B2

9 VDC Battery

Battery

Holder

Figure 9 - Installing Field Wiring for

Auxiliary Contacts

Connects to BAS/SCADA system

Auxiliary Contacts

White - Common

Red - Normally Closed

Black - Normally Open

Class 2, 24 VDC/VAC(50/60HZ)

500 milliamps

MAXIMUM!

Jam
Nut

2 wire cable

To BAS/SCADA

1/2" Strain

Relief

Use #8 X 1 1/4"

Self Tapping Screws

1/2" Electrical

Knockout

Center

Screw

Base

Base

Wire Nuts

Plastic

Cord

Holder

OilTector

Cover

Terminal Block

connects to terminal

blocks 6 & 7 of the

CONTROL PANEL

Figure 10

7000 Apple Tree Avenue, Bergen, NY 14416 Phone: (800) 543-2550-Fax: (585) 494-1839-www.libertypumps.com

Operation and Maintenance Manual

Page 4 of 6

DWG#7235000H

Manual 7235000H

The OilTector Remote Alarm Panel is powered by 120 VAC coming from standard wall outlets and is transformed to 9VDC.

Installing a 9 Volt battery provides battery back-up.
When the OilTector Control Panel’s Auxiliary Contacts “close” the buzzer and light will turn “on” and the alarm panel’s auxiliary

contacts will be activated. Pressing the “silence switch deactivates the buzzer and auxiliary contacts. When the OilTector Control

Panel’s Auxiliary Contacts reset, the remote alarm panel will automatically reset itself.
Test product weekly. Make sure the green ”power on” light is “on”. Press the “Test” switch; the red alarm light and buzzer should

turn “on”. If the battery back up system is utilized, unplug the wall mount power supply (the green light will be off). Now press the

“Test” switch; the red alarm light and buzzer will turn “on”. If the buzzer sounds less loudly than when tested with the normal power

supply, then replace the battery.
1. To install/replace the battery for the backup power feature, remove the two side screws and install 9 VDC battery (Duracell

model MX 1604B2). After installing battery, press the test button to activate the alarm to make sure the battery works properly.

Reinstall side screws. See Figures 7.
2. Determine mounting location for the Alarm Panel. Make sure power outlet is within 6 feet of the alarm. Make sure the outlet

is on a separate circuit breaker from any other device and not on a switched receptacle to maintain power integrity. Mount the

alarm using two #8 x 1 1/4" self tapping screws (not included). Use #8 plastic anchor if mounting to sheet rock. See Figure 8.

The alarm can be mounted up to 2500 feet from the panel using 18 ga wire.
3. If Auxiliary Contacts are used, continue; otherwise go to step 4. Remove cover from base and remove 1/2" electrical knockout

from base. Use 16 - 2 AWG stranded wire - make sure there is at least 6" of wire inside of enclosure. Install a 1/2" strain relief

with jam nut. Connect wires for required application using wire nuts. Caution ! - When installing wires, route all wires away from

sharp objects & internal components. See figures 9 & 10.
4. There are two terminals on the bottom of the alarm panel. Connect a wire from the first terminal to the CONTROL PANEL

terminal #6 and connect another wire from the second terminal of the alarm panel to CONTROL PANEL terminal #7. See Figure

8
5. Plug the power supply into a 120VAC, 50/60 HZ standard wall outlet. For UL applications, remove center screw on receptacle

and place cord from wallmount transformer inside the plastic cord holder. Secure plastic cord holder to the receptacle by reinstall

ing screw to the center hole of receptacle. See Figure 8. For Canadian applications DO NOT INSTALL Plastic Cord Holder! The

green "Normal" light should come on.
6. Test the system by pressing the "Test" switch. The buzzer and the red warning light will be "on". The green "Normal" light will

be "off". While holding the “Test” switch, press the “Silence” switch. The buzzer will silence, but the alarm light will remain “on”.

Let go of the “Test” switch and the alarm light will turn “off” and the green “Normal” light will turn “On” indicating the system is now

in a normal condition.

Operation and Maintenance Manual

Operation and Maintenance Manual

Operation and Maintenance Manual

Installation of the Alarm Panel