Discharge lines, Alignment – Gorman-Rupp Pumps 86A2-F3L 1257390 thru 1330588 User Manual
Page 12
80 SERIES
OM--00955
PAGE B -- 5
INSTALLATION
OPERATING
RANGE
(See Table Below)
CABLE
TETHER
POINT
OFF
(Emptying)
ON
(Filling)
ON
(Emptying)
OFF
(Filling)
1.25” Pipe
(Not Furnished)
ENGINE
CONTROL
BOX
1.0
(0.3)
APPROXIMATE FREE CORD LENGTH IN FT. (M)
0.5
(.15)
1.0
(0.3)
1.5
(.46)
2.0
(0.6)
2.5
(.76)
3.0
(0.9)
2.0
(0.6)
3.0
(0.9)
4.0
(1.2)
Figure 3. Float Switch Data
DISCHARGE LINES
Siphoning
Do not terminate the discharge line at a level lower
than that of the liquid being pumped unless a si-
phon breaker is used in the line. Otherwise, a si-
phoning action causing damage to the pump
could result.
Valves
If a throttling valve is desired in the discharge line,
use a valve as large as the largest pipe to minimize
friction losses. Never install a throttling valve in a
suction line.
With high discharge heads, it is recommended that
a throttling valve and a system check valve be in-
stalled in the discharge line to protect the pump
from excessive shock pressure and reverse rota-
tion when it is stopped.
If the application involves a high discharge
head, gradually close the discharge
throttling valve before stopping the pump.
Bypass Lines
If a system check valve is used due to high dis-
charge head, it may be necessary to vent trapped
air from the top of the pump during the priming
process. This may be accomplished by installing a
bypass line from the top of the pump, back to the
source of liquid. The end of the bypass line must be
submerged. The line must be large enough to pre-
vent clogging, but not so large as to affect pump
discharge capacity.
ALIGNMENT
The alignment of the pump and engine are critical
for trouble-free performance. See Section E,
Se-
curing Intermediate And Drive Assembly To En-
gine in MAINTENANCE AND REPAIR, for details.