beautypg.com

Alignment – Gorman-Rupp Pumps T4A60S-F3L 1264856 thru 1314224 User Manual

Page 17

background image

OM-05512

SUPER T SERIES

PAGE B - 10

INSTALLATION

DISCHARGE PIPE

DISCHARGE

CHECK VALVE

PUMP DISCHARGE

SELF‐PRIMING

CENTRIFUGAL

PUMP

SUCTION

LINE

SUPPORT

BRACKET

CLEAN‐OUT

COVER

INSTALL AIR RELEASE VALVE

IN HORIZONTAL POSITION

90

_ LONG

RADIUS

ELBOW

BLEED LINE 1”

(25,4 MM) DIA. MIN.

(CUSTOMER FUR‐
NISHED) EXTEND 6”

(152,4 MM) BELOW

PUMP OFF LIQUID
LEVEL

WET WELL

OR SUMP

Figure 7. Typical Automatic Air Release Valve Installation

The valve inlet line must be installed between the
pump discharge port and the non‐pressurized side
of the discharge check valve. The valve inlet is at
the large end of the valve body, and is provided
with standard 1 inch NPT pipe threads.

The valve outlet is located at the opposite end of
the valve, and is also equipped with standard 1
inch NPT pipe threads. The outlet should be con­
nected to a bleed line which slopes back to the wet
well or sump. The bleed line must be the same size
as the inlet piping, or larger. If piping is used for the
bleed line, avoid the use of elbows whenever pos­
sible.

NOTE

It is recommended that each Air Release Valve be

fitted with an independent bleeder line directed
back to the wet well. If multiple Air Release Valves
are installed in a system, they must be fitted with in­
dependent bleeder lines; never use a common
manifold pipe. Contact your Gorman‐Rupp distrib­
utor or the Gorman‐Rupp Company for information
about installation of an Automatic Air Release Valve
for your specific application.

ALIGNMENT

The alignment of the pump and the engine is criti­
cal for trouble‐free mechanical operation. See Sec­
tion E, Securing Intermediate And Drive Assem­
bly To Engine
for detailed information.