INSTALLATION
DISCHARGE PIPE
DISCHARGE
CHECK VALVE
PUMP DISCHARGE
SELF-PRIMING
CENTRIFUGAL
PUMP
SUCTION
LINE
SUPPORT
BRACKET
CLEAN-OUT
COVER
INSTALL AIR RELEASE VALVE
IN HORIZONTAL POSITION
90
_ LONG
RADIUS
ELBOW
BLEED LINE 1"
(25,4 MM) DIA. MIN.
(CUSTOMER FUR-
NISHED) EXTEND 6"
(152,4 MM) BELOW
PUMP OFF LIQUID
LEVEL
WET WELL
OR SUMP
Figure 7. Typical Automatic Air Release Valve Installation
The valve inlet line must be installed between the
pump discharge port and the non-pressurized side
of the discharge check valve. The valve inlet is at
the large end of the valve body, and is provided
with standard 1 inch NPT pipe threads.
The valve outlet is located at the opposite end of
the valve, and is also equipped with standard 1
inch NPT pipe threads. The outlet should be con-
nected to a bleed line which slopes back to the wet
well or sump. The bleed line must be the same size
as the inlet piping, or larger. If piping is used for the
bleed line, avoid the use of elbows whenever pos-
sible.
NOTE
It is recommended that each Air Release Valve be
fitted with an independent bleeder line directed
back to the wet well. If multiple Air Release Valves
are installed in a system, they must be fitted with in-
dependent bleeder lines; never use a common
manifold pipe. Contact your Gorman-Rupp distrib-
utor or the Gorman-Rupp Company for information
about installation of an Automatic Air Release Valve
for your specific application.
ALIGNMENT
The alignment of the pump and the engine is criti-
cal for trouble-free mechanical operation. See Sec-
tion E, Securing Intermediate And Drive Assem-
bly To Engine for detailed information.