Figure 3G

Pull and connect the 80mm (3-1/8 in.) corrugated pipe to

the water heater’s flue tube reducer with hi-temp red silicone

and gear clamp. Make sure this connection is tight and leak

proof.

*The sealant between 80mm (3-1/8 in.) corrugated pipe

and water heater’s flue tube reducer must be hi-temp red

silicone or other material suitable for 315°C (600°F) con-

tinuous service.

Figure 3H

Apply silicone around 152mm (6 in.) collar on air manifold

box. Pull corrugated vent tube all the way on to collar and

secure with one sheet metal screw (approx. 19mm (3/4

in.) up from edge of vent tube. Pull gear clamp past screw

and tighten.

Figure 3J

Check the vent pipe’s level or slope again, and adjust if

required.

Offset Vent Pipe Arrangement

Figure 3K - CONDITION 1

Where a straight vent pipe arrangement is impossible, a

horizontal 90 degree maximum bend can be made. Use

the water heater casing outer diameter as a template to

form the corrugated pipe.

Figure 3L - CONDITION 2

Where floor joists impede venting, a rise to complete the

vent termination is possible. All installations require

25mm (1 in.) clearance to combustibles.

Note:

A. The maximum horizontal vent pipe length of 2.28m

(90 in.) minus wall thickness should be considered

when installing an offset vent arrangement.

B. Do not combine condition (3K) with condition (3L)

in the same installation.

- 5 -

SLOPE

TOP VIEW

90° MAXIMUM

BEND

WALL 254mm

(10 in.) (REF)

MINIMUM

(SEE TEXT)

>25mm (1 in.)

>25mm (1 in.)