beautypg.com

26 appendix b - specifications, Inputs, Input performance – West Control Solutions MRC 5000 Controller Manual User Manual

Page 26

background image

26

Appendix B - Specifications

INPUTS

Input Types/Range

Type

Range

Thermocouple

J

0

°

C to 760

°

C

0

°

F to 1400

°

F

K

0

°

C to 1360

°

C

0

°

F to 2500

°

F

T

-200

°

C to 400

°

C

-330

°

F to 750

°

F

R

200

°

C to 1650

°

C

400

°

F to 3000

°

F

S

200

°

C to 1650

°

C

400

°

F to 3000

°

F

RTD

100 ohm Platinum

-140

°

C to 400

°

C

-220

°

F to 750

°

F

.00385 ohms/ohm/

°

C

Current DC

0 to 20mA, 4 to 20mA
Internal 4.7 ohm Shunt Resistor

Voltage DC

0 to 25mV, 0 to 50mV, 10 to 50mV, 0 to 5 V, 1 to 5 V

Impedance

> 100M ohm for TC and mV inputs
100K ohms for 5V inputs
4.7 ohms for mA inputs

RTD Excitation Current

150 microamps, typical

Input Scan Rate

1 scan per second for non-RTD inputs
1 scan per 1.2 seconds for RTD inputs

Input Correction

Offset Adjustment, -999 to 999 units

Sensor Fault Detection

Display goes to "SnSr" and pen goes upscale if a sensor break is detected
No sensor break can be detected for zero based Volt and Milliamp ranges
Display goes to "Hi" 10% above span.
Display goes "Lo" 10% below span or zero, whichever is higher.

.

INPUT PERFORMANCE

Performance Under Reference Condition:
Measurement Error

Type J, K, T, R, S, and RTD:

±

0.25% of span

±

1 degree

mA, mV, and VDC:

±

0.25% of scaled span plus 1 least significant digit

Cold Junction Compensation Error

±

0.2

°

C @ 25

°

C

Cold Junction Compensation Rejection

0.04

°

/

°

C deviation from 25

°

C

Linearization Error

TCs:

±

0.25

°

C typical,

±

0.5

°

C worst case with expectations

RTDs:

±

0.1

°

C typical,

±

0.3

°

C worst case

Ambient Temperature Error

±

0.01% of span per

°

C deviation from 25

°

C

Common Mode Rejection

>120 dB at 50/60 Hz, 260 VAC max.

Normal Mode Rejection

85 dB minimum @60Hz or greater

Isolation

Universal input isolated from all outputs at 240VAC
Inputs share a common signal ground

Reference Conditions
Ambient Temperature

25

°

C

Relative Humidity

60 - 70%

Supply Voltage

115 VAC, 60 Hz

Source Resistance

< 10 ohms for TC input

Lead Resistance

< 0.1 ohm/lead balanced (Pt100)