FLOW RATES

Settings will vary when used to sense flow of other
fluids or if located in a vertical pipe.

3

NOTE: DO NOT USE LIQUID FLOW SWITCHES

ON SYSTEMS WITH FLOW VELOCITY

GREATER THAN 10 FEET PER SECOND

(3 METERS PER SECOND).

Values are ± 10%

Pipe

Mode of Operation

Size NPT

Flow

No Flow

in. (mm)

Settings

gpm (lpm)

gpm (lpm)

Factory or

1 (25)

Minimum

6

(22.7)

3.6

(13.6)

27

Maximum

10.2

(38.6)

9.2

(34.8)

(102)

Factory or

1

1

4

(32)

Minimum

9.8

(37.1)

5.6

(21.2)

47

Maximum

16.8

(63.6)

15

(56.8)

(178)

Factory or

1

1

2

(40)

Minimum

12.7

(48.1)

7

(26.5)

63

Maximum

23

(87.1)

19.5 (73.8)

(239)

Factory or

2 (50)

Minimum

18.8

(71.2)

9.4

(35.6)

105

Maximum

32.8 (124.1)

24

(90.8)

(398)

Factory or

2

1

2

(65)

Minimum

24.3

(92)

11.6 (43.9)

149

Maximum

42.4 (160.5)

37.5 (141.9)

(565)

Factory or

3 (80)

Minimum

30

(113.6)

12

(45.4)

230

Maximum

52.1 (197.2)

46.1 (174.5)

(872)

Factory or

4 (100)

Minimum

39.7 (150.3)

19.8 (74.9)

397

Maximum

73.5 (278.2)

64.2

(242)

(1505)

Factory or

5 (125)

Minimum

58.7 (222.2)

29.3 (110.9)

654

Maximum

115 (435.3)

92

(348.2)

(2479)

Factory or

6 (150)

Minimum

79.2

(300)

39.6

(150)

900

Maximum

166 (628.3)

123 (465.6)

(3411)

Max. Flow

Rate gpm

(lpm) w/o

Paddle Damage

calculated using clean water in a horizontal pipe.

Flow rates required to activate the flow switch

are shown in chart below.These values were

NOTE: THIS PRODUCT IS NOT INTENDED

FOR USE IN POTABLE WATER

APPLICATIONS.