PUMP
OPERATION

BURNER
OPERATION

FROM BURNER OR ALARM

CONTROL CIRCUIT

TO ALARM

CONTROL CIRCUIT

TO BURNER

CONTROL CIRCUIT

FROM PUMP UP

CONTROL CIRCUIT

TO PUMP UP

CONTROL CIRCUIT

NEUTRAL

HOT

BCOM

BNC

BNO

PCOM

PNC

PNO

N

H

g

f

e

d

c

b

a

• Connect wire “a” from power supply to terminal “H”.
• Connect wire “b” from neutral supply to terminal “N”.
• Connect wire “c” from pump control circuit to terminal “PNO”.
• Connect wire “d” from pump control circuit to terminal “PCOM”.
• Connect wire “e” from burner control circuit to terminal “BNO”.
• Connect wire “f” from alarm control circuit to terminal “BNC”.
• Connect wire “g” from burner or alarm control circuit to terminal “BCOM”.

WIRING DIAGRAMS
Low Water Cut-Off, Alarm and Pump Up Control

PUMP 1
OPERATION

PUMP 2
OPERATION

FROM PUMP #1

CONTROL CIRCUIT

FROM PUMP #2

CONTROL CIRCUIT

TO PUMP #2

CONTROL CIRCUIT

TO PUMP #1

CONTROL CIRCUIT

NEUTRAL

HOT

BCOM

BNC

BNO

PCOM

PNC

PNO

N

H

f

e

d

c

b

a

• Connect wire “a” from power supply to terminal “H”.

• Connect wire “b” from neutral supply to terminal “N”.

• Connect wire “c” from pump #1 control circuit to terminal “PNO”.

• Connect wire “d” from pump #1 control circuit to terminal “PCOM”.

• Connect wire “e” from pump #2 control circuit to terminal “BNC”.

• Connect wire “f” from pump #2 control circuit to terminal “BCOM”.

Dual Pump Control

VALVE
SPRING
CLOSED

BURNER
OPERATION

VALVE
DRIVE
TO OPEN

• Connect wire “a” from power supply to terminal “H”.

• Connect wire “b” from neutral supply to terminal “N”.

• Connect wire “c” from valve control circuit to terminal “PNO”.

• Connect wire “d” from valve control circuit to terminal “PCOM”.

• Connect wire “e” from burner control circuit to terminal “BNO”.

• Connect wire “f” from alarm control circuit to terminal “BNC”.

• Connect wire “g” from burner or alarm control circuit to terminal “BCOM”.

Motorized Valve and Low Water Cut-Off

FROM VALVE

CONTROL CIRCUIT

TO VALVE

CONTROL CIRCUIT

NEUTRAL

HOT

BCOM

BNC

BNO

PCOM

PNC

PNO

N

H

d

c

b

a

FROM BURNER OR ALARM

CONTROL CIRCUIT

TO ALARM

CONTROL CIRCUIT

TO BURNER

CONTROL CIRCUIT

g

f