Duplex three phase wiring diagram – d3 – Xylem Wastewater (Technical Manual) User Manual
Page 22

PAGE 22
Wastewater
Goulds Water Technology, Bell & Gossett,
Red Jacket Water Products, CentriPro
L1
L3
S1
1
2
1
2
PUMP
NO. 2
WHITE
CONTROL
ON-OFF
BLACK
BLACK
YELLOW
ORANGE
HAND
OFF
AUTO
BLUE
S2
RUN
HAND
OFF
AUTO
PURPLE
S1
RUN
RED
TEST
RED
YEL
YELLOW
BRW
BROWN
TEST
MUTE
RESET
SILENCE
RESET
HORN
FLASH
PINK
WHITE
RED
FLASHING
SONALERT
OFF
LEAD
LAG
ALARM
R1
R2
C
L1
N
BLACK
H
L1
N
1
2
3
4
5
6
7
8
9
10
11
J1➀
OFF FLOAT➁
LEAD FLOAT
LAG FLOAT
(OPTIONAL)③
ALARM FLOAT
J2
DRY CONTACTS
③
FACTORY WIRED FOR (3) FLOAT
OPERATION. FOR (4) FLOAT
OPERATION, REMOVE JUMPER (J2)
FROM TERMNALS (6) AND (8).
INSTALL LAG FLOAT ON
TERMINALS (5) AND (6).
➀
FOR SEPARATE 120 VAC
CONTROL POWER SUPPLY,
REMOVE JUMPER (J1) FROM
TERMINALS (H) AND (L1).
CONNECT 15 AMP MAX.
PROTECTED 120 VAC SUPPLY
TO TERMINALS (L1) AND (N).
WITH THE NEUTRAL OF THE
SUPPLY TO (N).
➁
FOR USE WITH WIDE ANGLE
FLOAT SWITCH (ONE FLOAT FOR
BOTH ON AND OFF OPERATION).
JUMP TERMINALS (3) AND (4),
INSTALL WIDE ANGLE FLOAT TO
TERMINALS (1) AND (2).
208/230/460/575 VAC
THREE PHASE
60 Hz
2 A
3
T
S2
L2
1
2
PUMP
NO. 1
3
T
FACTORY WIRED FOR 460 VAC. FOR 208, 230 OR
FOR 575 VAC OPERATION CHANGE CONTROL TRANSFORMER
PRIMARY AT TERMINAL BLOCK.
75 VA
120 VAC
575
VA
C
460
VA
C
230
VA
C
208
VA
C
ALTERNATOR SWITCH
PUMP 1
ALT
PUMP 2
ALTERNATOR SWITCH –
STANDARD ON ALL DUPLEX
PANELS, THIS SWITCH PROVIDES
OPTIONS FOR: ALTERNATE
PUMPS, USE ONLY PUMP 1 OR
USE ONLY PUMP 2. IT IS USED
WHEN A PUMP IS REMOVED
FOR SERVICE.
Duplex Three Phase Wiring Diagram – D3 — — — —