4 maximum value is ready to be programmed. The

currently programmed maximum motor speed value is
shown on the 3-DIGIT LCD.

4 Enter the motor speed at the maximum mA input

signal value. Press the FIELD button to select the
digit to program. The digit will blink when selected.

4 Press the DIGIT button to change the selected digit.

4 Repeat until all digits are programmed.

4 Press the mode button. The % SPEED icon will stop

blinking and the mA icon will blink indicating the
maximum mA value is ready to be programmed. The
currently programmed maximum value is shown on
the 3-DIGIT LCD.

4 Enter the maximum mA input signal value. Note: this

value must be greater than the minimum mA input
signal value. Press the FIELD button to select the digit
to program. The digit will blink when selected..

4 Press the DIGIT button to change the selected digit.

4 Repeat until all digits are programmed.

4 Press the mode button. Programming is complete.

4 To exit the programming mode, press the

RUN/STANDBY button and the MODE button at the
same time. The PROGRAM arrow will disappear.

PROGRAM MODE 2

% speed at the maximum input

RUN

PROGRAM

STAND-BY

PRIME

MINIMUM

MAXIMUM

% SPEED

2

MODE

100

PROGRAM MODE 2

maximum input value

RUN

PROGRAM

STAND-BY

PRIME

MINIMUM

MAXIMUM

2

MODE

20.0

mA

Example 1

6

4

8 10 12 14 16 18 20

0

25

50

75

100

Pump

Motor

S

p

eed

(%)

Milliamp input (mA)

4 mA = 0% OUTPUT

20 mA = 100% OUTPUT

Example 2

6

4

8 10 12 14 16 18 20

0

25

50

75

100

Pump

M

otor

S

p

eed

(%)

Milliamp input (mA)

4 mA = 100% OUTPUT

20 mA = 0% OUTPUT

Example 4

6

4

8 10 12 14 16 18 20

0

25

50

75

100

Pump

Motor

S

p

eed

(%)

Milliamp input (mA)

4 mA = 20% OUTPUT

20 mA = 50% OUTPUT

MODE 2 PROGRAMMING EXAMPLES