4 maximum value is ready to be programmed. The
currently programmed maximum motor speed value is
shown on the 3-DIGIT LCD.
4 Enter the motor speed at the maximum mA input
signal value. Press the FIELD button to select the
digit to program. The digit will blink when selected.
4 Press the DIGIT button to change the selected digit.
4 Repeat until all digits are programmed.
4 Press the mode button. The % SPEED icon will stop
blinking and the mA icon will blink indicating the
maximum mA value is ready to be programmed. The
currently programmed maximum value is shown on
the 3-DIGIT LCD.
4 Enter the maximum mA input signal value. Note: this
value must be greater than the minimum mA input
signal value. Press the FIELD button to select the digit
to program. The digit will blink when selected..
4 Press the DIGIT button to change the selected digit.
4 Repeat until all digits are programmed.
4 Press the mode button. Programming is complete.
4 To exit the programming mode, press the
RUN/STANDBY button and the MODE button at the
same time. The PROGRAM arrow will disappear.
PROGRAM MODE 2
% speed at the maximum input
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
% SPEED
2
MODE
100
PROGRAM MODE 2
maximum input value
RUN
PROGRAM
STAND-BY
PRIME
MINIMUM
MAXIMUM
2
MODE
20.0
mA
Example 1
6
4
8 10 12 14 16 18 20
0
25
50
75
100
Pump
Motor
S
p
eed
(%)
Milliamp input (mA)
4 mA = 0% OUTPUT
20 mA = 100% OUTPUT
Example 2
6
4
8 10 12 14 16 18 20
0
25
50
75
100
Pump
M
otor
S
p
eed
(%)
Milliamp input (mA)
4 mA = 100% OUTPUT
20 mA = 0% OUTPUT
Example 4
6
4
8 10 12 14 16 18 20
0
25
50
75
100
Pump
Motor
S
p
eed
(%)
Milliamp input (mA)
4 mA = 20% OUTPUT
20 mA = 50% OUTPUT
MODE 2 PROGRAMMING EXAMPLES
C-1100V