2-10 SDI-12 Command and Response Protocol

H-335

Example of a H-335 Extended "Read Coefficient" command:

Command

Response

Time Values

Description

"aXRC3!"

"a0011"

1 sec 1

Read Coefficient 3

(gate radius)

Subsequent Command

Response

"aD0"

a+36.000

2.10 Extended “Read Coefficient” Command

The H-335 processes the sensor measurement data with a set of coefficients. Each coefficient is

programmable, allowing the H-335 to be used on gates with different geometries, and to scale the

height and distance output values to user desired engineering units. This command allows the user

to read any of the coefficients. At the factory the coefficients are set to the following values.

Coefficient

Default Value

Description

C1

+1.0

User angle slope (compensates for clockwise or counter-

clockwise mounting )

C2

0.0

User angle offset (provides zero output with gate against sill)

C3

36.0 (Feet)

Gate Radius (determines user units; inches, feet etc.)

C4

51.05756 Degrees

Sill Angle (angle of the gate sill with respect to trunnion

bearing)

Command

Response

Description

"aXRCn!"

"a0011"

Read Coefficient

Where:

a

is the sensor address ("0-9", "A-Z", "a-z", "*", "?").

XRC

are upper case characters

n

is coefficient number 1 to 4.

This command takes 001 seconds to complete and places 1 value in the data buffer. Use the “aD0"

command to collect and view the data.