4 modbus checklist, Modbus checklist – YSI IQ SensorNet MIQ/A-MOD Module User Manual
Page 21
MIQ/(A-)MOD
Interface for the Modbus RTU
21
ba76021e01
01/2012
3.4
Modbus checklist
The following checklist supports you when planning, projecting and
installing a Modbus plant with the IQ S
ENSOR
N
ET
. For smooth
operation, you should be able to answer all questions with "Yes".
Is the [bus system] (bus segment) installed without branch lines?
Was the correct Modbus cable used (cord type A according to
EN 50170)?
Are the poles of the signal lines A line and B line correctly connected
at all bus connections?
Is it guaranteed that there is no short-circuit between A line, B line
and cable shielding?
Is the shielding installed free of interruptions?
Are the guidelines for shielding and grounding being observed, and
doesn't any unallowed potential equalization current flow
via the shielding?
Is the maximum cable length (per bus segment) observed for the
corresponding baud rate?
Do all devices support the required baud rate?
Are exactly two terminators switched on at the ends of the [bus
system] (bus segment)?
Are the terminators supplied with voltage so the following applies:
U
B line
- U
A line
> + 500 mV?
Do all devices have individual bus addresses?
Have the devices been restarted after changing the bus address,
baud rate or parity (switched off and then on again)?
Do the addresses projected in the master correspond to the actual
addresses?
After commissioning:
Do all devices signal error-free behavior?
Is it guaranteed that the Modbus master has consistent access
to the 16 byte sensor data structure?