beautypg.com

Earth (ground) connections, Pump package location guidelines, Foundation requirements – Xylem AquaBoost CS and VS Pumping Packages User Manual

Page 27

background image

Earth (ground) connections

WARNING:
Electrical shock hazard. Conduit grounds are not adequate. You must attach a separate
earth (ground) wire to the earth (ground) lug provided in the enclosure in order to avoid
potential safety hazards. Failure to follow these instructions can result in serious personal
injury, death, or property damage.

A grounding terminal is provided for a dedicated earth (ground) wire connection. You
must follow all provisions of the National Electrical Code and local codes.

Pump package location guidelines

WARNING:
Assembled units and their components are heavy. Failure to properly lift and support this
equipment can result in serious physical injury and/or equipment damage. Lift equipment
only at the specifically identified lifting points. Lifting devices such as eyebolts, slings, and
spreaders must be rated, selected, and used for the entire load being lifted.

Guideline

Explanation/comment

Make sure that the space around the pump package is

sufficient.

This facilitates ventilation, inspection, maintenance, and

service.

If you require lifting equipment such as a hoist or tackle,

make sure that there is enough space above the pump

package.

This makes it easier to properly use the lifting equipment

and safely remove and relocate the components to a safe

location.

Protect the unit from weather and water damage due to

rain, flooding, and freezing temperatures.

This is applicable if nothing else is specified.

Do not install and operate the equipment in closed

systems unless the system is constructed with properly-

sized safety and control devices.

Acceptable devices:

• Pressure relief valves
• Compression tanks
• Pressure controls
• Temperature controls
• Flow controls

If the system does not include these devices, consult the

engineer or architect in charge before you operate the

pump.

Take into consideration the occurrence of abnormal noise

and vibration.

The best pump location for noise and vibration

absorption is on a concrete floor with subsoil underneath.

Foundation requirements

Requirements

• The foundation must be able to absorb any type of vibration and form a permanent,

rigid support for the unit.

• The foundation must weigh at least 2-1/2 times the weight of the pump unit.
• Provide a flat, substantial concrete foundation in order to prevent strain and distortion

when you tighten the foundation bolts.

• Sleeve-type and J-type foundation bolts are most commonly used. Both designs allow

movement for the final bolt adjustment.

• Tie the concrete pad in with the finished floor.

Installation

AquaBoost CS and VS Pumping Packages Installation, Operation, and Maintenance Manual

25