1XXXX MAPPING - MODBUS DISCRETE INPUTS / AQUAVAR STATUS WORD
Modbus Ref.
Internal Location
R/W
Indication
Value
10001
Status Word - Bit 0
R
READY
1 = READY,
0 = NOT READY
10002
Status Word - Bit 1
R
ENABLED
1 = ENABLED,
0 = NOT ENABLED
10003
Status Word - Bit 2
R
STARTED
1= STARTED,
0 = NOT STARTED
10004
Status Word - Bit 3
R
Reserved (Not Used)
10005
Status Word - Bit 4
R
ZERO_SPEED
1 = 0 Hz,
0 = > 0 Hz
10006
Status Word - Bit 5
R
ACCELERATE
1 = ACCELERATING,
0 = NOT ACCELERATING
10007
Status Word - Bit 6
R
DECELERATE
1 = DECELERATING,
0 = NOT DECELERATING
10008
Status Word - Bit 7
R
AT_SPEED
1 = MAX FREQUENCY,
0 = NOT MAX FREQUENCY
10009
Status Word - Bit 8
R
Reserved (Not Used)
10010
Status Word - Bit 9
R
Reserved (Not Used)
10011
Status Word - Bit 10
R
Reserved (Not Used)
10012
Status Word - Bit 11
R
Reserved (Not Used)
10013
Status Word - Bit 12
R
PANEL_LOCAL
0 = NOT LOCAL
1 = LOCAL
10014
Status Word - Bit 13
R
Reserved (Not Used)
10015
Status Word - Bit 14
R
EXT2_ACT
0 =Speed Control Mode
1 = All Other Macros
10016
Status Word - Bit 15
R
FAULT
0 = NO FAULT,
1 = FAULT
10017
Status Word - Bit 16
R
ALARM
0 = NO ALARM,
1 = ALARM
10018
Status Word - Bit 17
R
REQ_MAINT
10019
Status Word - Bit 18
R
Reserved (Not Used)
10020
Status Word - Bit 19
R
LOCAL LOCK
0 = LOCAL LOCK OFF,
1 = LOCAL LOCK ON
10021
Status Word - Bit 20
R
Reserved (Not Used)
10022
Status Word - Bit 21
R
Reserved (Not Used)
10023
Status Word - Bit 22
R
Reserved (Not Used)
10024
Status Word - Bit 23
R
Reserved (Not Used)
10025
Status Word - Bit 24
R
Reserved (Not Used)
10026
Status Word - Bit 25
R
Reserved (Not Used)
10027
Status Word - Bit 26
R
Reserved (Not Used)
10028
Status Word - Bit 27
R
Reserved (Not Used)
10029
Status Word - Bit 28
R
Reserved (Not Used)
10030
Status Word - Bit 29
R
Reserved (Not Used)
10031
Status Word - Bit 30
R
Reserved (Not Used)
10032
Status Word - Bit 31
R
Reserved (Not Used)
10033
DI1
R
DI1
0 = OFF, 1 = ON
10034
DI2
R
DI2
0 = OFF, 1 = ON
10035
DI3
R
DI3
0 = OFF, 1 = ON
10036
DI4
R
DI4
0 = OFF, 1 = ON
10037
DI5
R
DI5
0 = OFF, 1 = ON
10038
DI6
R
DI6
0 = OFF, 1 = ON
Supported Function Codes
02 - Read Input Status