4XXXX REGISTER MAPPING
DRIVE PARAMETERS
Modbus Ref.
Contents
R/W
Remarks
40002
Reference 1
R/W
Use for Speed Control Macro Only
Range = 0 … 10000 (0 … 100.00%)
40003
Reference 2 (Setpoint)
R/W
Remote Setpoint via Modbus
Range = 0 … 10000 (0 … 100.00%) of Transducer range.
e.g. 0 = 0 psi and 10000 = 300 PSI.
NOTE: Group 16 Setpoint Select must be set to Fieldbus
40005
Actual 1
(Select using 3210)
R
By default, stores nothing. Use parameter 3210 to
select an actual value for this register.
e.g. 3210 = 0101, 40006 = Motor Freq.
40006
Actual 2
(Select using 3211)
R
By default, stores nothing. Use parameter 3211 to
select an actual value for this register.
40007
Actual 3
(Select using 3213)
R
By default, stores nothing. Use parameter 3213 to
select an actual value for this register.
40008
Actual 4
(Select using 3214)
R
By default, stores nothing. Use parameter 3214 to
select an actual value for this register.
40009
Actual 5
(Select using 3214)
R
By default, stores nothing. Use parameter 3215 to
select an actual value for this register.
40010
Actual 6
(Select using 3214)
R
By default, stores nothing. Use parameter 3216 to
select an actual value for this register.
40011
Actual 7
(Select using 3214)
R
By default, stores nothing. Use parameter 3217 to
select an actual value for this register.
40012
Actual 8
(Select using 3214)
R
By default, stores nothing. Use parameter 3218 to
select an actual value for this register.
40031
Aquavar Control Word LSW
R/W
Maps directly to the Least Significant Word of the
Aquavar profile’s CONTROL WORD.
40032
Aquavar Control Word MSW
R
Maps directly to the Most Significant Word of the
Aquavar profile’s CONTROL WORD.
40033
Aquavar Status Word LSW
R
Maps directly to the Least Significant Word of the
Aquavar profile’s STATUS WORD.
40034
Aquavar Status Word MSW
R
Maps directly to the Most Significant Word of the
Aquavar profile’s STATUS WORD.
Group 1
VFD Signal
R/W
Set Value (Dec)
40101
Motor Frequency
R
—
40102
Motor Current
R
—
40103
Motor Power
R
—
40104
DC Bus Voltage
R
—
40105
Motor Voltage
R
—
40106
Drive Temp
R
—
40107
VFD On Time
R
—
40108
Run Time
R
—
40109
KWh Counter
R
—
40110
DI6-1 Status
R
—
40111
AI1
R
—
40112
AI2 Trnsdcr Fdbk
R
—
40113
RO3-1 Status
R
—
40114
AO1 (mA)
R
—
40115
AO2 (mA)
R
—
40116
Last Fault
R
—
40117
Previous Fault 1
R
—
40118
Previous Fault 2
R
—