Factory Direct Hardware Von Duprin 6221 User Manual
Installation instructions, 6221 electric strike
Installation Instructions
6221 Electric Strike
®
4. Test strike: Apply solenoid power. Fail secure (FSE) lip unlocks.
Fail safe (FS) lip locks.
5. Install strike with two #12-24 screws. Make sure clearance
between latch bolt and strike lip is 1/32” (Figure 2). If not,
uninstall strike, adjust (Figure 3), and reinstall.
6. Test door: With strike unlocked, door opens with latch bolt
extended. When door closes, latch bolt rides over strike lip.
931224_00(5) Copyright © 2004 Ingersoll-Rand. All rights reserved.
89/336/EEC
Notes: Deadbolt will not function with this strike.
Check with factory for retrofit applications.
1. For lock or device preparation, see their directions.
2. Prepare door for strike (see other side).
3. Wire strike (Figure 1).
Double Door Open Back Mortise or Cylindrical Application
Figure 1
Yellow solenoid wires = 12 VDC, 0.57 A
Black solenoid wires = 24 VDC, 0.29 A
(also shown on strike label)
SOLENOID POWER REQUIREMENTS
DC input is
nonpolarized.
NOTE
!
J1
P1
P1 J1A
P1A
SO-12 or SO-24
12 VDC
or
24 VDC
12 VAC SO-12 12 VDC
or
24 VAC SO-24 24 VDC
{
{
Wiring
for DC
supply
Wiring
for AC
supply
Solenoid
Use crimp
connectors to
splice field wiring
to P1 leads
Figure 2
Top view;
faceplate not
shown for clarity
1/32”
Latch bolt
Strike lip
Figure 3
To adjust strike,
loosen screws A, B,
and C and move
backbox sideways
as necessary
A
B
C
931224_5
931224_5
931224_5
931224_5
931224_5
PREPUBLICA
TION
REVIEW COPY REV. A
931224-00