DRYER CONTROLLER FACTORY DEFAULT PROGRAM SETTINGS


DRY

CYCLE

COOL

DOWN TIME

(MINUTES)

TOTAL

CYCLE TIME

(MINUTES)

DRYING

TEMPERATURE

(

0

F) (

0

C)

DRYER LOAD

1

5

35

180

82

Towels, pads, heavy cotton

2

2

20

170

77

Sheets, blended materials

3 5

25

180

82

Cotton

4 2

20

130

54

Synthetic

materials

5 2

25

175

79

Blended

materials

DRYER FAULT CODES


FAULT#

FAULT

DESCRIPTION

ACTION

F1

Shorted thermostat

sensor.

Dryer stops and “F1” flashes on the 4-digit display. When

short circuit on sensor input is removed, “LOAd” appears on

the 4-digit display and the remaining dry time is reset.

F2

Open thermostat

sensor.

Dryer stops and “F2” flashes on the 4-digit display. When a

good sensor is connected to sensor input, “LOAd” appears on

the 4-digit display and the remaining dry time is reset.

F3

EEPROM
corrupted.

Dryer will not start and “F3” appears on the 4-digit display.

The power to the dryer must be cycled to reset the controller.

Fault should only occur when starting a dry cycle.

F4

Gas valve on fault.

The drying temperature did not increase 1

º

F. in 15 minutes.

“F4” will flash on the display and the dry cycle will finish

without calling for heat (energizing gas valve). Opening the

door or pressing the STOP key will reset the fault and clear the

remaining time in the dry cycle.

F5 Temperature

fault.

The drying temperature is at least 25

º

F. above the temperature

setting. “F5” will flash on the 4-digit display and the dry cycle

will finish without calling for heat (energizing the gas valve).

The power to the dryer must be cycled to reset the controller.