beautypg.com

Table 2. setting t – Rainbow Electronics MAX6645 User Manual

Page 6

background image

MAX6643/MAX6644/MAX6645

There are two options for the behavior of the PWM out-
puts at power-up. Option 1 (minimum duty cycle = 0):
at power-up, the PWM duty cycle is zero. Option 2
(minimum duty cycle = the start duty cycle): at power-
up, there is a startup delay, after which the duty cycle
goes to 100% for the spin-up period. After the startup
delay and spin-up, the duty cycle drops to its minimum
value. The minimum duty cycle is in the 0% to 50%
range (see the Selector Guide).

To control fan speed based on temperature, T

HIGH

is

set to the temperature beyond which the fan should spin
at 100%. T

LOW

is set to the temperature below which

the duty cycle can be reduced to its minimum value.
After power-up and spin-up (if applicable), the duty
cycle reduces to its minimum value (either 0% or the
start duty cycle). For option 1 (minimum duty cycle = 0),
if the measured temperature remains below T

HIGH

, the

duty cycle remains at zero (see Figure 1). If the temper-
ature increases above T

HIGH

, the duty cycle goes to

100% for the spin-up period, and then goes to the start
duty cycle (for example, 40%). If the measured temper-
ature remains above T

HIGH

when temperature is next

measured (4s later), the duty cycle begins to increase,
incrementing by 1.5% every 4s until the fan is spinning
fast enough to reduce the temperature below T

HIGH

.

For option 2 (minimum duty cycle = start duty cycle), if
the measured temperature remains below T

HIGH

, the

duty cycle does not increase and the fan continues to
run at a slow speed. If the temperature increases
above T

HIGH

, the duty cycle begins to increase, incre-

menting by 1.5% every 4s until the fan is spinning fast
enough to reduce the temperature below T

HIGH

(see

Figure 2). In both cases, if only a small amount of extra
cooling is necessary to reduce the temperature below

Automatic PWM Fan-Speed Controllers with
Overtemperature Output

6

_______________________________________________________________________________________

Table 2. Setting T

LOW

(MAX6643 and MAX6644)

STARTUP

DUTY CYCLE

TEMPERATURE

TIME

TIME

T

HIGH

SPIN-UP

T

LOW

Figure 1. Temperature-Controlled Duty-Cycle Change with
Minimum Duty Cycle 30%

STARTUP

MAX664_B HAS 30% PWM_OUT DUTY CYCLE DURING STARTUP.

DUTY CYCLE

TEMPERATURE

TIME

TIME

T

HIGH

T

LOW

SPIN-UP

Figure 2. Temperature-Controlled Duty-Cycle Change with
Minimum Duty Cycle 30%

TL2

TL1

T

LOW

(°C)

L SUFFIX

T

LOW

(°C)

H SUFFIX

0

0

15

35

0

High-Z

20

40

0

1

25

45

High-Z

0

30

50

High-Z

High-Z

35

55

High-Z

1

40

60

1

0

45

65

1

High-Z

50

70

1

1

55

75

High-Z = High impedance.