PNEG-524 Roof Exhaust Fan

7. Electrical Installation

Electrical Installation of the Fan

The electrical installation must be performed by a certified electrician in accordance with the appropriate
national and local electrical codes.

Check the type of electrical service present and make sure the fan to be wired is manufactured to
operate on the electrical service. The table

on Page 11

entitled “Fan Model Specifications” indicates

the electrical service the fan is designed to utilize in the column labeled “Motor Phase and Voltage”.
The electrical service must match this specification.

The components to connect the electrical service to the fan need to be sized for the electrical service
present. The charts below illustrate the sizing information for

1 Phase 230 Volt

,

3 Phase 230 Volt

and 460 Volt

respectively. Use the appropriate information and size the following electrical

service components:

Electrical Service for 1 Phase Operation 230 Volt

Electrical Service for 3 Phase Operation 230 Volt

Electrical Service for 3 Phase Operation 460 Volt

Transformer

The transformer size for the fan only is indicated in a KVA rating. Example: For a 24" fan the first chart
would be used. The KVA rating for the 2 HP motor is 3-1/2 KVA. This KVA rating is for the fan only.
The electrician will need to add the KVA requirements for the other electrical components of the system
in sizing the transformer.

Motor

HP Range

Transformer Size

(Note B) (Minimum)

Copper Wire Size for Distance - Motor to

Disconnect in Feet up to:

Fusetron or

Equivalent Time

Delay Fuse AMP

0'-50'

100' 200'

300'

0.5

1.0 KVA

14

14

12

10

10

2.0

3.5 KVA

12

10

6

5

30

Motor

HP Range

Transformer Size

(Note B) (Minimum)

Copper Wire Size for Distance - Motor to

Disconnect in Feet up to:

Fusetron or

Equivalent Time

Delay Fuse AMP

0'-50'

100' 200'

300'

0.5

1.0 KVA

14

14

14

14

10

2.0

3.5 KVA

14

12

10

8

15

Motor

HP Range

Transformer Size

(Note B) (Minimum)

Copper Wire Size for Distance - Motor to

Disconnect in Feet up to:

Fusetron or

Equivalent Time

Delay Fuse AMP

0'-50'

100' 200'

300'

0.5

1.0 KVA

14

14

14

14

10

2.0

3.5 KVA

14

14

12

12

10

CAUTION

Any violation of electrical wiring codes could jeopardize the airstream warranty.